FireSpy Tracker Operation Manual
5
reset will return the panel to its normal operating condition. To perform the fast reset, press the
RESET
button. The panel completes a fast reset in approximately 5-10 seconds.
Forced reset
The forced reset is similar to the fast reset, except that non-resettable events are forced to reset. To force
a reset, press and hold the
RESET
button until the panel starts to reset (approx. 5 seconds). After the
panel has restarted, it is likely that some events will reactivate because the condition that caused them is
still present. The panel completes a forced reset in approximately 5-10 seconds.
Full reset
The full reset powers down all circuits, even non-resettable circuits, during the reset. All modules perform
their startup initialization. To perform a full reset, press
PROG
to enter the passcode screen, then press
RESET
. If you are in programming mode and press
RESET
, this is the type of reset that occurs. The panel
completes a full reset in approximately 20-30 seconds, with SLCs completing their startup 10-20 seconds
after that.
Table 2-1: Annunciator Buttons
Button
Action (normal mode*)
C
D
Browse forward or backward through alarm event list
A
B
Browse forward or backward through the non-alarm event list
ACK
NOWLEDGE
Turn off the annunciator’s buzzer
SILENCE
Turn off building notification and other outputs activated by off-normal events. The SILENCE LED
flashes when this button is activated.
RESET
Reset devices that are in alarm to a normal condition. See 2.4.1 for details.
Fast Reset: press
RESET
Forced Reset: press and hold
RESET
Full Reset: press
PROG
, then press
RESET
.
Alphanumeric keypad
(other than 0)
Used for programming only.
PROG
Enter the menu system.
*
Refer to the programming sections of this manual and the programming manual for the programming mode functions of
the buttons.