beautypg.com

B5 a 4, 4using the menu system – Harrington Signal Tracker T8000 - Operation Manual User Manual

Page 17

background image

B

5

A

4

HSI #780-0923

FireSpy Tracker Operation Manual

13

4

Using the menu system

4.1

Accessing the menu system

To access the menu system, press the

PROG

key and enter the access code for the desired level. The

default code for Level 1 (maintenance functions) is 11111111. The default code for Level 2 (programming
functions) is 22222222.

The SLCs must finish their startup before the menu system can be accessed. The SLC startup takes 10-
30 seconds after the panel is reset.

4.2

Exiting the menu system

The changes you make are saved after you press

ENTER

on each screen. There is no extra step to save

changes before exiting the menu system. To leave the menu system at any time, press

RESET

; this will

also reset the panel.

4.3

About the numbering used

Each menu in this manual is given a number based on how to navigate to it starting from the main menu:

A number means press the number to select an option.

A letter indicates which "more" screen the option is chosen from (A is the first screen, press

C

to get

to B, the second screen).

Levels are separated by periods.

So to navigate to the Level 2 Menu 1.2B from normal standby press

PROG

(enter the passcode for

Level 2), press 1 for child menu 1, press 2 for child menu 2, then press

C

to get to the second screen of

options.

4.4

Menu navigation

Display

The display shows available menu options.

Available keys

0

to

9

go to child menu corresponding to number

E

go back to parent menu

RESET

exit the menu system and reset the panel

Program Menu

1. Clock

2. System Options

3. RS-485 Settings

4. Input Settings

5. Output Settings

6. Point Settings

7. Group Settings

4.5

Assign a setting

Display

When a screen shows some values to change, highlight the value you
wish to change and then change it.

Available keys

C / D

: highlight the value you wish to change

A / B

: change the highlighted value

E

go back to parent menu

ENTER

go back to parent menu and save changes

RESET

exit the menu system and reset the panel

Serial Port Config

Mode: PC Link

Dial Number:

Modem Init String:

This manual is related to the following products: