FireSpy Tracker Operation Manual

2

The programming technician is ultimately responsible for conformance to the applicable codes and
purchase order.

This manual cannot cover all details or contingencies which could exist in a system application. Refer to
the authorized distributor if additional information is required.

Specifications are subject to change without notice.

1.2

Settings not allowed by regulations

NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES

This product incorporates field-programmable software. In order for the product to comply with
regulations, certain programming features or options must be limited to specific values or not used at all
as indicated below.

Feature or

option

Regulation*

Settings not allowed

Settings allowed

Alarm verification

36.5.3, 36.6.3

Alarm verification is not permitted on any
device that is used as part of the cross-
zone or multiple detector initiating
operation.

Verify that alarm verification is not used on
any device used in cross-zone or multiple
detector initiation.

Abort switch

36.3.1

Abort switches shall not be used on
systems intended to perform pre-action or
deluge water functions.

Do not assign the abort or halt function to
modules used in the releasing operation.

Time delay

36.1.7

An automatic delay provided prior to
release operation by a system shall be a
maximum of 60 seconds.

Verify that the time delay is set to 60
seconds or less.

* Sections cited are from the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864 ninth edition

1.3

Warranty

Harrington Signal products are covered by a limited warranty. See Harrington’s warranty statement for
more details (document #780-0762).CPG products are covered by a limited warranty. See CPG’s
warranty statement for more details.

1.4

Support

If you have any questions or concerns about installation, operation, or programming of our equipment,
please contact us at:

Harrington Signal Inc.
Commercial Products Group
2519 – 4

th

Ave

Moline, IL 61265

Toll Free: (800) 577-5758
Phone:

(309) 762-0731

Fax:

(309) 762-8215

Email:

[email protected]

Web:

Email:

[email protected]

Web:

www. cpglifesafety.com

FireSpy is a registered trademark of Harrington Signal Inc.
This document is copyright © 2009-2011 Harrington Signal Inc. All rights reserved.

This manual is related to the following products: