Co nt en ts – Harrington Signal Tracker T8000 - Operation Manual User Manual
Page 10
![background image](/manuals/591931/10/background.png)
Co
nt
en
ts
1
2
HSI #780-0923
FireSpy Tracker Operation Manual
6
2.5
System conditions and annunciation
2.5.1
Normal standby condition
Display
The system is considered to be in normal standby condition unless an off-
normal condition or event occurs.
The log of previous events can be viewed from this screen by pressing
ENTER
until the bottom of the screen shows
Activity Journal
and then
press one of the arrow keys. To exit viewing the log, stop pressing
buttons until the display returns to the normal standby screen (about 45
seconds).
Audible and visual indicators
The buzzer is off, and all visual indicators are off, except for POWER,
which is on.
Available keys
ENTER
toggle which type of log to view (active or journal)
C D
view next/prev alarm or supervisory alarm event in log
A B
view next/prev trouble event in selected log
RESET
hold to perform forced reset
PROG/RESET
perform full reset
PROG
enter maintenance or programming menus
[BANNER MESSAGE 1]
[BANNER MESSAGE 2]
T1000 Vers 6.00
[date] [day] [time]
2.5.2
Non-normal condition (event counter)
Display
When there are active events, the display shows a counter for each type
of possible event. If an alarm is present, the lower portion of the display
will show information about the alarm event.
Audible and visual indicators
The buzzer sounds a pattern according to the highest priority event type
and the system LEDs corresponding to active events are turned on.
Available keys
SILENCE
(If all events are acknowledged) Silence notification devices.
ACK
Acknowledge all events and turn off the buzzer.
(If all events are acknowledged) Toggle the list browsed by the
right/left arrow keys (Active Troubles or Activity Journal).
RESET
Press once to reset alarm events.
Press and hold to reset conventional zone alarm events.
To restart the panel, press
PROG
and then
RESET
.
C / D
Step backwards/forwards through the list of alarm/supervisory
events
A / B
Step backwards/forwards in time through the Active Trouble list or
Activity Journal
PROG
Enter programming mode
Active Events
ALARM-0000 SUPV-0000
PRALM-0000 TBL-0001
(alarm present)
Active Events
ALARM-0001 SUPV-0000
PRALM-0000 TBL-0001
01/01/11 Su 12:00:00
001-Device in Alarm
Lobby Photo Smoke