HSI #780-0923

FireSpy Tracker Operation Manual

Appendix B. Operating instructions

Frame these instructions and place adjacent to the panel for ready reference

Condition

Description and some common responses

Normal standby

When the system is operating normally and there are no off-normal conditions, the
green AC POWER light is on and the display screen shows the banner message.

Alarm

In case of alarm, the ALARM light flashes, the buzzer sounds, and display screen
shows the oldest alarm event. Audible and visual notification devices and remote
alarm signals operate.

To view alarm conditions:
Press

C

/

D

keys to browse through alarm events.


To silence the alarm:

WARNING: For Authorized Personnel Only

This will silence audible NACs and change panel indications to the alarm silenced
condition.

Acknowledge the reported events by pressing

ACK

.

Verify that no waterflow or other non-silenceable devices are involved.

Wait until the alarm silence inhibit timer has expired, if in use.

Press

SILENCE

.


To reset the panel:

NOTE:

Any normally-energized relay control devices operated
by the system may momentarily reverse on panel reset.

Only after the alarm condition is cleared, press RESET to return the panel to standby
operation.

Trouble

When the system detects a trouble, the TROUBLE light flashes, the panel buzzer
sounds, and the trouble event shows on the display screen.

If the trouble has not been cleared within 24 hours, the trouble display will return to
its initial condition and the buzzer will sound.

WARNING: Some trouble conditions may prevent response to a fire

alarm.


To view trouble conditions:
Press

A / B

keys to browse through trouble events.


To silence the trouble buzzer:

Press

ACK

to acknowledge. The buzzer will silence and the resound timer will

start.


If service is required, contact the installer or local Harrington dealer below.