Appendix b. operating instructions, Firespy tracker operating instructions – Harrington Signal Tracker T8000 - Operation Manual User Manual
Page 25

HSI #780-0923
FireSpy Tracker Operation Manual
Appendix B. Operating instructions
Frame these instructions and place adjacent to the panel for ready reference
Condition
Description and some common responses
Normal standby
When the system is operating normally and there are no off-normal conditions, the
green AC POWER light is on and the display screen shows the banner message.
Alarm
In case of alarm, the ALARM light flashes, the buzzer sounds, and display screen
shows the oldest alarm event. Audible and visual notification devices and remote
alarm signals operate.
To view alarm conditions:
Press
C
/
D
keys to browse through alarm events.
To silence the alarm:
WARNING: For Authorized Personnel Only
This will silence audible NACs and change panel indications to the alarm silenced
condition.
•
Acknowledge the reported events by pressing
ACK
.
•
Verify that no waterflow or other non-silenceable devices are involved.
•
Wait until the alarm silence inhibit timer has expired, if in use.
•
Press
SILENCE
.
To reset the panel:
NOTE:
Any normally-energized relay control devices operated
by the system may momentarily reverse on panel reset.
Only after the alarm condition is cleared, press RESET to return the panel to standby
operation.
Trouble
When the system detects a trouble, the TROUBLE light flashes, the panel buzzer
sounds, and the trouble event shows on the display screen.
If the trouble has not been cleared within 24 hours, the trouble display will return to
its initial condition and the buzzer will sound.
WARNING: Some trouble conditions may prevent response to a fire
alarm.
To view trouble conditions:
Press
A / B
keys to browse through trouble events.
To silence the trouble buzzer:
•
Press
ACK
to acknowledge. The buzzer will silence and the resound timer will
start.
If service is required, contact the installer or local Harrington dealer below.
Name
Address
Phone/Fax
FireSpy Tracker
Operating Instructions