beautypg.com

Table 32 — economi$er+ inputs and outputs, Table 33 — start-up mode sequence – Bryant 580F User Manual

Page 54

background image

54

Table 32 — EconoMi$er+ Inputs and Outputs

*If there are 3 stages then there can only be 1 stage of power exhaust.
†If there are 4 stages then there will not be power exhaust stages that will be directly controlled.

Table 33 — Start-Up Mode Sequence

LED — Light-Emitting Diode

INPUT

NAME

TYPE

USE

INPUT/OUTPUT

RANGE

CONVERSION

RANGE

CONVERSION

RESOLUTION

CONNECTION

PIN NO.

THERMOSTAT INPUTS
Y1 (Cool/Low Cool)

Y1

Switch

Standard

18-30 vac 50/60 Hz w/min 24 mA Load

NA

On/Off

J1

1

Y2 (Cool 2/High Cool)

Y2

Switch

Option

18-30 vac 50/60 Hz w/min 24 mA Load

NA

On/Off

J1

2

G (fan)

G

Switch

Standard

18-30 vac 50/60 Hz w/min 24 mA Load

NA

On/Off

J1

3

Occupied/Unoccupied

OCC

Switch

Option

18-30 vac 50/60 Hz w/min 24 mA Load

NA

On/Off

J1

4,5

POWER
Power

24V

Input

Standard

18-30 VAC 50/60 Hz

NA

NA

J2

1,2

ECONOMIZER MOTOR
Control

CNT

2-10 vdc

Standard

2-10 vdc

0-100%

1%

J2

3,4,5

ANALOG INPUTS
Supply Air Temperature

SAT

10 K Thermistor

Standard

1816 to 86407 Ohms

30 to 125 F

0.8 F

J3

1,2

Outside Air Temperature

OAT

10 K Thermistor

Standard

1816 to 86407 Ohms

30 to 125 F

0.8 F

J3

3,4

Return Air Temperature

RAT

10 K Thermistor

Option

1816 to 86407 Ohms

30 to 125 F

0.8 F

J3

5,6

Indoor Humidity

IRH

4-20 mA,

Loop Powered

Option

4-20 mA, 24 vdc

0-100%

.08 mA

J3

7,8,9

Outdoor Humidity

ORH

4-20 mA,

Loop Powered

Option

4-20 mA, 24 vdc

0-100%

.08 mA

J3

10,11,12

Indoor CO

2

IAQ

4-20 mA,

Ext Sourced

Option

4-20 mA, 24 vdc

0-200 PPM/10

10 PPM

J3

13,14

Remote Minimum
Position Pot

MIN

10K

Option

10K to 100K Ohms

0 to 100%

1%

J3

15,16,17

RELAY OUTPUTS
Cooling Stage 1

CP1

Relay

Standard

24 vac, 2.5 Amps at 24 vac

NA

On/Off

J4

1,3,4

Cooling Stage 2

CP2

Relay

Option

24 vac, 2.5 Amps at 24 vac

NA

On/Off

J4

2,3,4

Power Exhaust 2/
Cooling Stage 3*

CP3/

EX2

Relay

Option

24 vac, 2.5 Amps at 24 vac

NA

On/Off

J4

5,6

Power Exhaust 1/
Cooling Stage 4†

CP4/

EX1

Relay

Option

24 vac, 2.5 Amps at 24 vac

NA

On/Off

J4

5,7

DISPLAY
Setpoint Switch 1

SP1

Digital

Standard

Open/Closed

Logic

Open/Closed

On Board

NA

Setpoint Switch 2

SP2

Digital

Standard

Open/Closed

Logic

Open/Closed

On Board

NA

LED 1

DS1

LED Output

Standard

Red

Logic

On/Off

On Board

NA

LED 2

DS2

LED Output

Standard

Yellow

Logic

On/Off

On Board

NA

LED 3

DS3

LED Output

Standard

Green

Logic

On/Off

On Board

NA

LED 4

DS4

LED Output

Standard

Green

Logic

On/Off

On Board

NA

TIME

LED 1/DS1 (RED)

LED 2/DS2 (YELLOW)

LED 3/DS3 (GREEN)

LED 4/DS4 (GREEN)

0-1.0 SEC

OFF

OFF

OFF

OFF

1-1.5 SEC

FLASH ½ SEC

OFF

OFF

OFF

1.5-2.0 SEC

OFF

FLASH ½ SEC

OFF

OFF

2.0-2.5 SEC

OFF

OFF

FLASH ½ SEC

OFF

2.5-3.0 SEC

OFF

OFF

OFF

FLASH ½ SEC