Lassic, Eries, 3/4 “ conduit connections (x 3) – Watts F1113-12RFP User Manual
Page 5
Globe
Angle
C
lassiC
s
eries
12541 Gulf Freeway
•
Houston, Texas 77034
•
(Ph) 713.943.0688
•
(Fx) 713.944.9445
•
www.watts.com
Relay with
Red LED
Indicator
15
10
20
5
25
0
30
SEC
Power
UP
L N G 1 2 3 4 5 6
Incoming Power
120V, 1 PH
(Field Terminated)
FS-99
Flow Sensor
(Field Terminated)
Solenoid
( by factory)
3/4 “ Conduit Connections (x 3)
6.00
8.00
CERTIFIED ELECTRICIAN TO CONNECT MAIN POWER
AND FS99 FLOW SENSOR TO JB113 JUNCTION BOX
JB113 Junction Box
The valve mounted JB113 Junction Box is a lockable NEMA 4 enclosure equipped with an adjustable time delay,
electrical relay and terminal strip. There are three 3/4 inch conduit connections. The valve solenoid is prewired.
The valve is normally open and closes drip-tight when continuous relief valve discharge through the drain pipe is
sensed by the FS99 Flow Sensor.
The valve mounted JB113 Junction Box is equipped with an adjustable time delay to avoid valve closure due to
intermittent or nuisance relief valve discharge. The time delay is adjusable from 0-30 seconds.
Adjusting the dial clockwise increases the time delay for valve closure. Adjusting the dial counterclockwise de-
creases the time delay for valve closure.
F113-12RFP (Globe)
F1113-12RFP (Angle)