beautypg.com

Lassic, Eries, 3/4 “ conduit connections (x 3) – Watts F1113-12RFP User Manual

Page 5

background image


Globe


Angle

C

lassiC

s

eries

12541 Gulf Freeway

Houston, Texas 77034

(Ph) 713.943.0688

(Fx) 713.944.9445

www.watts.com

Relay with

Red LED

Indicator

15

10

20

5

25

0

30

SEC

Power

UP

L N G 1 2 3 4 5 6

Incoming Power

120V, 1 PH

(Field Terminated)

FS-99

Flow Sensor

(Field Terminated)

Solenoid

( by factory)

3/4 “ Conduit Connections (x 3)

6.00

8.00

CERTIFIED ELECTRICIAN TO CONNECT MAIN POWER

AND FS99 FLOW SENSOR TO JB113 JUNCTION BOX

JB113 Junction Box

The valve mounted JB113 Junction Box is a lockable NEMA 4 enclosure equipped with an adjustable time delay,

electrical relay and terminal strip. There are three 3/4 inch conduit connections. The valve solenoid is prewired.

The valve is normally open and closes drip-tight when continuous relief valve discharge through the drain pipe is

sensed by the FS99 Flow Sensor.

The valve mounted JB113 Junction Box is equipped with an adjustable time delay to avoid valve closure due to

intermittent or nuisance relief valve discharge. The time delay is adjusable from 0-30 seconds.

Adjusting the dial clockwise increases the time delay for valve closure. Adjusting the dial counterclockwise de-

creases the time delay for valve closure.

F113-12RFP (Globe)

F1113-12RFP (Angle)