beautypg.com

Approvals – standards, Assembly flow orientation, Material specifications – Watts 007M1DCDA User Manual

Page 2: Pressure specification, Temperature specifications, Configurable options, Example ordering descriptions, Performance, Dimensions — weights

background image

Approvals – Standards

• Approved by the Foundation for Cross-Connection Control and

Hydraulic Research at The University of Southern California

(FCCCHR-USC)

• ASSE 1048 Listed
• UL Classified (US & Canada)
• FM Approved
• IAPMO/cUPC
• AWWA Standard C510 Compliant
• NFPA 13, 14, 15, 16, 20, 22 & 24 Compliant
• End Connections OS&Y Gate Valves – Compliant to ASME

B16.1 Class 125 & AWWA Class D Flange

Assembly Flow Orientation

• Horizontal - Approved by FCCCHR-USC, ASSE, UL, FM,

IAPMO/cUPC

• Vertical Up - Approved by FCCCHR-USC, ASSE, UL, FM,

IAPMO/cUPC

Material Specifications

• Body: Cast Bronze ASTM B584
• Elastomers: Silicone
• O-Rings: EPDM
• Check Modules: Engineered Plastics

Pressure Specification

• Max. Working Pressure: 175psi
• Min. Working Pressure: 10psi
• Hydrostatic Test Pressure: 350psi
• Hydrostatic Safety Pressure Rating: 700psi

Temperature Specifications

• Continuous Operating Range: 33°F-110°F (0.5°C-43°C)
• Intermittent Operating Range up to 140°F (60°C)

Must not exceed 12 hour duration

Configurable Options

(Prefix – Suffix)

Suffix
OSY: UL/FM Approved OS&Y Gate Valves (ANSI/AWWA C515

Compliant)

CFM: Totalizing Cubic Feet/Minute

5

8

"x

3

4

" Water Meter (ANSI/

AWWA C700 Compliant)

GPM: Totalizing Gallons/Minute

5

8

"x

3

4

" Water Meter (ANSI/

AWWA C700 Compliant)

LF:

Less Shutoff valves; This is NOT an APPROVED

ASSEMBLY

Example Ordering Descriptions

2" 007M1DCDA-OSY-GPM - Valve Fitted with OS&Y Shutoff &

Gallon per Minute Water Meter
2" 007M1DCDA-LF-CFM – Non-Approved Device with Cubic

Feet per Minute Water Meter & No Shutoff Valves

Performance

Flow capacity chart identifies valve performance based upon

rated water Velocity up to 20fps
• Maximum service flow rate is determined by maximum rated

Velocity of 7.5fps.

• AWWA Manual M-22 (Appendix C) recommends that the maxi-

mum water Velocity in the services be not more than 10fps.

• UL flow rate is determined by typically rated Velocity of 15 fps.

MODEL

SIZE (DN)

DIMENSIONS

WEIGHT

A

B

C

D

in.

mm

in.

mm

in.

mm

in.

mm

in.

mm

lbs.

kgs.

007M1DCDA-OSY

2

50

22

5

8

575

10

9

16

268

11

13

16

300

13

1

2

343

85

38.6

C

A

B

D

(Open)

psi

22
20
18
16
14
12
10

8
6
4
2
0

0 20 40 60 80 100 120 140 160 180 200 220 240 260

gpm

76 152 228 303 378 454 530 606 680 757 833 908 984

lpm

7.5

16.3 24.5

fps

PSI DROP

(*Friction loss)

Rated Flow

100%Rated Flow

*UL Rated Flow

Dimensions — Weights

1048

(OSY only)

ES-007M1DCDA 1333

© 2013 Watts

USA: Tel: (978) 688-1811 • Fax: (978) 794-1848 • www.watts.com

Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 • www.watts.ca

A Watts Water Technologies Company