Approvals – standards, Assembly flow orientation, Material specifications – Watts 007M1DCDA User Manual
Page 2: Pressure specification, Temperature specifications, Configurable options, Example ordering descriptions, Performance, Dimensions — weights

Approvals – Standards
• Approved by the Foundation for Cross-Connection Control and
Hydraulic Research at The University of Southern California
(FCCCHR-USC)
•	ASSE	1048	Listed
•	UL	Classified	(US	&	Canada)
•	FM	Approved
•	IAPMO/cUPC
•	AWWA	Standard	C510	Compliant
•	NFPA	13,	14,	15,	16,	20,	22	&	24	Compliant
•		End	Connections	OS&Y	Gate	Valves	–	Compliant	to	ASME	
B16.1 Class 125 & AWWA Class D Flange
Assembly Flow Orientation
• Horizontal - Approved by FCCCHR-USC, ASSE, UL, FM,
IAPMO/cUPC
• Vertical Up - Approved by FCCCHR-USC, ASSE, UL, FM,
IAPMO/cUPC
Material Specifications
•	Body:	Cast	Bronze	ASTM	B584
•	Elastomers:	Silicone
•	O-Rings:	EPDM
•	Check	Modules:	Engineered	Plastics
Pressure Specification
•	Max.	Working	Pressure:	175psi
•	Min.	Working	Pressure:	10psi
•	Hydrostatic	Test	Pressure:	350psi
•	Hydrostatic	Safety	Pressure	Rating:	700psi
Temperature Specifications
•	Continuous	Operating	Range:	33°F-110°F	(0.5°C-43°C)
•		Intermittent	Operating	Range	up	to	140°F	(60°C)	 
Must not exceed 12 hour duration
Configurable Options
(Prefix – Suffix)
Suffix
OSY:	 	UL/FM	Approved	OS&Y	Gate	Valves	(ANSI/AWWA	C515	
Compliant)
CFM: Totalizing Cubic Feet/Minute
5
⁄
8
"x
3
⁄
4
" Water Meter (ANSI/
AWWA C700 Compliant)
GPM: Totalizing Gallons/Minute
5
⁄
8
"x
3
⁄
4
" Water Meter (ANSI/
AWWA C700 Compliant)
LF:
Less Shutoff valves; This is NOT an APPROVED
ASSEMBLY
Example Ordering Descriptions
2" 007M1DCDA-OSY-GPM - Valve Fitted with OS&Y Shutoff &
Gallon per Minute Water Meter
2"	007M1DCDA-LF-CFM	–	Non-Approved	Device	with	Cubic	
Feet per Minute Water Meter & No Shutoff Valves
Performance
Flow capacity chart identifies valve performance based upon
rated	water	Velocity	up	to	20fps
•		Maximum	service	flow	rate	is	determined	by	maximum	rated	
Velocity of 7.5fps.
• AWWA Manual M-22 (Appendix C) recommends that the maxi-
mum water Velocity in the services be not more than 10fps.
• UL flow rate is determined by typically rated Velocity of 15 fps.
MODEL
SIZE (DN)
DIMENSIONS
WEIGHT
A
B
C
D
in.
mm
in.
mm
in.
mm
in.
mm
in.
mm
lbs.
kgs.
007M1DCDA-OSY
2
50
22
5
⁄
8
575
10
9
⁄
16
268
11
13
⁄
16
300
13
1
⁄
2
343
85
38.6
C
A
B
D
(Open)
psi
22
20
18
16
14
12
10
8
6
4
2
0
0 20 40 60 80 100 120 140 160 180 200 220 240 260
gpm
76 152 228 303 378 454 530 606 680 757 833 908 984
lpm
7.5
16.3 24.5
fps
PSI DROP
(*Friction loss)
Rated Flow
100%Rated Flow
*UL Rated Flow
Dimensions — Weights
1048
(OSY only)
ES-007M1DCDA 1333
© 2013 Watts
USA: Tel: (978) 688-1811 • Fax: (978) 794-1848 • www.watts.com
Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 • www.watts.ca
A Watts Water Technologies Company