Watts 007M1DCDA User Manual
Model 007m1dcda, For non-health hazard commercial fire applications, Now available
For Non-Health Hazard Commercial Fire Applications
ES-007M1DCDA
Job Name –––––––––––––––––––––––––––––––––––––––––––
Contractor ––––––––––––––––––––––––––––––––––––––––––––
Job Location –––––––––––––––––––––––––––––––––––––––––
Approval –––––––––––––––––––––––––––––––––––––––––––––
Engineer –––––––––––––––––––––––––––––––––––––––––––––
Contractor’s P.O. No. ––––––––––––––––––––––––––––––––––
Approval –––––––––––––––––––––––––––––––––––––––––––––
Representative ––––––––––––––––––––––––––––––––––––––––
2" (50mm) 007M1DCDA-OSY-GPM
Now Available
WattsBox Insulated Enclosures.
For more information, refer to literature ES-WB.
Model 007M1DCDA
Residential Fire Sprinkler
Double Check Detector Backflow
Prevention Assembly
Sizes: 2" (50mm)
The Model 007M1DCDA Double Check Detector Assembly is
specifically designed to protect against possible backpressure
and backsiphonage conditions for non-health hazard (i.e., pol-
lutant) application in accordance with Local Governing Water
Utility Code. This assembly is primarily used on commercial
fire sprinkler systems where Local Governing Code mandates
protection from non-potable quality water being pumped or
siphoned back into the potable water system.
Typical Installation
The Model 007M1DCDA is typically installed for service on
commercial fire sprinkler systems. It is recommended this
device is installed after a water meter and/or main line isolation
shut-off valve with installation techniques that comply with the
latest edition of the Uniform Plumbing Code. Please consult
Local Governing Code for proper installation and agency code
requirement.
This Engineering Sheet is not intended to replace the product
installation and safety information available or the experience of
a trained product installer. Please refer to the product installa-
tion and safety instructions for further information.
Features
Main Valve
• Compact Design for Ease of Installation
• Inline Serviceable Assembly
• No Special Tools Required for Servicing
• Captured Modular Spring Loaded Checks
• Field Replaceable Seats & Discs
• Field Replaceable Auxiliary Bypass Line & Components
Auxiliary Bypass
• Compact Bypass Design; Remains within Main Valve
Assembly Profile
• Inline Serviceable
1
⁄
2
" Backflow Assembly
• No Special Tools Required for Servicing
• Captured Modular Spring Loaded Checks
• Field Replaceable Seats & Discs
• Detect Potential Underground Water Leaks
• Detect Unauthorized Water Usage
Retainer
2nd Check
Module
1st Check
Module
Test Cocks
Product Specifications
The Model 007M1DCDA consists of a main line valve body
composed of two (2) independently acting approved poppet-
type check modules with replaceable seats and disc rubbers.
Servicing of both check modules do not require any special tools
and are accessed via a single top entry cover. This device is fit-
ted with approved UL Listed OS&Y Gate Valve Assemblies and
contains properly located resilient seated test cocks along the
main valve body.
The auxiliary bypass line contains a
5
⁄
8
"x
3
⁄
4
" (16 x 19mm) Water
Meter that complies with ANSI/AWWA Standard C700 coupled
with an approved double check assembly (DC). The bypass line
is design to detect leaks or unauthorized water usage of the
water system while protecting against possible backpressure
and backsiphonage conditions for non-health hazard (i.e., pollut-
ant) application.
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.
NOTICE
Inquire with governing authorities for local installation requirements