beautypg.com

Installation instructions, 2" (8 – 50mm) – Watts LF919 User Manual

Page 3

background image

3

WARNING:
Do not allow the drain line to empty directly into a drainage ditch, sewer system, or sump.
NOTE: Relief Valve Discharge Rates
The Series 919 and LF919 air gap and drain line terminating above a floor drain

can accommodate any moderate discharge or nuisance spitting through the

relief valve. However, to prevent water damage in the case of a catastrophic fail-

ure, you may need to design the floor drain size to accommodate the increased

discharge. Refer to Figure 1 for maximum relief valve discharge rates, size, and

capacity of typical floor drains.
NOTE: DO NOT reduce the size of the drain line from the air gap fitting. The drain

line must remain at full line size.
E. After initial installation of the Series 919 and LF919, a discharge from the relief

valve may occur due to dirt and pipe compounds. This may be due to inad-

equate initial flushing of the pipe lines. If flushing the valve does not clear the

unit, remove the first check valve and clean thoroughly, using the procedures

in "Servicing First & Second Check Valves" on page 6.

NOTE: Periodic relief valve discharge may occur on dead end service applications,

such as boiler feed lines or cooling tower makeup lines. This may be due to fluctuating

supply pressure during a static or no flow condition. To avoid this discharge, install a

spring-loaded, rubber seated check valve ahead of the backflow assembly.
F. It is recommended that you not place the Series 919 and LF919 in a pit or at

a depth below the ground level, unless absolutely necessary. If an installation

requires below ground level installation, a modified pit installation is recom-

mended, as well as the approval of local codes. In such cases, provision

should be made to always vent the drain line above the flood level. In the

case of a pit drain, ensure an adequate air gap exists between the bottom of

the drain line and the bottom of the pit.

G. It is recommended that periodic inspection of the Series 919 and LF919 be

done to check for any discharge from the relief valve. This discharge is a

visual indication that the valve needs cleaning or repair. In addition, it is rec-

ommended that periodic testing of the valve be done in compliance with local

codes to ensure its proper operation.

The relief vent discharges water during no-flow periods when:
(1) the first check valve is fouled; or
(2) the inlet pressure to the check valve drops sufficiently due to upstream pres-

sure fluctuations. This affects the required operating differential between the

inlet pressure and the reduced pressure zone; or

(3) the second check is fouled during emergency backflow or resulting from a

water hammer condition.

For troubleshooting guide send for literature S-TSG.
NOTE: When installing the Series 919 and LF919 on fire prevention systems,

special considerations are required.
Fire Protection System Installations: The National Fire Protection Agency (NFPA)

Guidelines require a confirming flow test be conducted by a certified tester when-

ever a “main line” valve is installed, such as a shutoff valve or a backflow preventer.

Installation Instructions

Series 919 and LF919

1

4

" – 2" (8 – 50mm)

1/2"
3/4" M2
1" M2

Typical Flow Rates as sized by floor drain manufacturers:

2"

55 GPM

5"

350 GPM

3"

112 GPM

6"

450 GPM

4"

170 GPM

8"

760 GPM

A. Shutoff Valves: If you remove the shutoff valves from the Series 919 and LF919, reassemble

the shutoff valve with the test cock mounted on the inlet side of the unit.

B. Always install the Series 919 and LF919 in an accessible location to facilitate testing and

servicing (See Page 2).

*Check the state and local codes to ensure that you install

the backflow preventer in compliance with those codes, such as the proper height

above the ground.

C. It is recommended that you install a strainer ahead of the Series 919 assemblies to protect

the internal components from unnecessary fouling.

CAUTION:

Do not install a Series 919 and LF919 with a strainer in rarely used water lines, such as a fire

sprinkler system which is only used during emergencies.
Start Up: Close the downstream shutoff. Open the upstream slowly and fill the valve. When the

valve is filled, open the downstream shutoff slowly, and fill the water supply system. This is nec-

essary to avoid water hammer and/or shock damage.
D. Vent the air gap and drain line from the relief valve in accordance with code requirements.

Terminate discharge approximately 12" (300mm) above the ground or through an air gap

piped to a floor drain.

45
40
35
30
25
20
15
10

5
0

0 10 20 30 40 50 60 70 80 90 100

110

Flow Rate gpm

Flow Rate gpm

Zone Pressure psi

0 10 20 30 40 50 60 70 80 90 100

110

Zone Pressure psi

1

4

" – 1" (8 – 25mm) 919 and LF919

Watts

1

4

" – 2" 919

*Vertical Flow Down

1

1

4

" – 2" (32 – 50mm) 919 and LF919

350
300
250
200
150
100

50

0

Floor Drain

Air

Gap

Elbow

Strainer

(32 – 40mm) (50mm)

1

4

"–

1

2

"

c

3

4

"

X 1"

(8 – 15mm)

(20mm)

(25mm)

0 1

1

4

"–1

1

2

" 2"

Figure 1

This manual is related to the following products: