Testing, Double check valve assemblies, Test no. 2 - test no. 2 check valve – Watts 774 User Manual
Page 7: Test no. 1 - test no. 1 check valve
![background image](/manuals/589954/7/background.png)
Test No. 2 - Test No. 2 Check Valve
1. Install high side hose between TC #3 and tester
connection A.
2. Install low side hose between TC #4 and tester
connection B.
3. Open TC #3 then VA, bleed hose, then close VA.
4. Open TC #4 then VB, bleed hose, then close VB.
5. Install a bypass hose between VB and TC #1. Open TC #1
and bleed by loosening hose connection at VB. Tighten
hose connection, fully open VB.
Push - Start Test
6. Close shutoff valve #1.
7. Slowly open VA and lower high side pressure about -2 psi
below the low side pressure (differential reading about -2.0
psi). Close VA. If reading is maintained, record as “tight”.If
reading returns to 0 and the pressure A increases to pres-
sure B, the check is recorded as leaking. If the reading re-
turns to + psi, No. 2 shutoff valve is leaking excessively,
and must be replaced to test the valve.
Push - Stop Test.
7
The following Test Procedure is one of several that is recognized
throughout the United States for verification of the functioning of
Backflow preventers.
The following procedure is not a specific recommendation.
The Watts series of test kits are capable of performing any
of the recognized Backflow test procedures.
A. Flush all test cocks.
B. Turn tester on (before connecting hoses). Tester must
read all zeroes. Close VA and VB.
Test No. 1 - Test No. 1 Check Valve
1. Install high side hose between TC #2 and tester
connection A.
2. Install low side hose between TC #3 and tester
connection B.
3. Open TC #2 then VA, bleed hose, then close VA.
4. Open TC #3 then VB, bleed hose, then close VB.
5. Install a bypass hose between VB and TC #1. Open TC #1
and bleed by loosening hose connection at VB. Tighten
hose connection, fully open VB.
Push - Print Head (wait) then Push - Star Test
6. Close shutoff valve #2 then #1.
7. Slowly open VA and loser high side pressure about -2 psi
below the low side pressure (differential reading about -2.0
psi). Close VA. If reading is maintained, record as “tight”.
If reading returns to 0 and the pressure A increases to
pressure B, the check is recorded as leaking. If the reading
returns to + psi, No. 2 shutoff valve is leaking excessively,
and must be replaced to test the valve.
8. Close all test cocks, remove hoses from TC #2 and TC #3
and TC #1. reopen shutoff valve #1. Proceed to Test No.2.
Push - Stop Test.
It is important that this device be tested periodically in compliance
with local codes, but at least once per year or more as service condi-
tions warrant. If installed on a fire sprinkler system all mechanical
checks, such as alarm checks, single checks and backflow preventers
should be inspected internally every one to five years in accordance
with NFPA 13 A and NFPA 25
Testing
Double Check Valve Assemblies
Watts 774
Watts TK-DP
Test 1
VA
VB
Watts 774
Watts TK-DP
Test 2
VA
VB
For additional testing information send for IS-TK-DP/DL, IS-TK-9A
and IS-TK-99E