Programming mode continued – Watts ProSense User Manual
Page 8
8
Level II Programming - P Values
Level II Programming parameters can be adjusted to fine-tune
the conditioner's operation. The parameters are accessible
by pressing and holding the UP and DOWN buttons until the
controller displays a "P" value.
NOTE: The controller must be in the home position to
change settings. See Table for Level II parameters.
Typically the Level II parameters will not need to
be adjusted as the default settings accommodate
most applications. Contact your water treatment
professional before attempting any programming.
Description
Range
Minimum
Increments
Default
Units
Notes
P9
Units of Measure
0-1
1
(2)
0 = US 1 = Metric
P10
Clock Mode
0-3
1
(2)
0 = 12 hour clock: flow rate displayed
1 = 24 hour clock: flow rate displayed
2 = 12 hour clock; Time of Day displayed
3 = 24 hour clock; Time of Day displayed
P11
Service Interval
0-99
1
0
Months
0 = Dissabled. Number of days per month is
fixed at 30.
P12*
Resin Tank Sensor
Placement
60-01
1
20
% of Capacity Expressed as a percentage of resin bed capacity
remaining after lowest set of pins.
P13
Disable Resin Tank
Sensors
0-1
1
0
0 = Resin Tank Sensors Enabled
1 = Resin Tank Sensors Disabled
P14
Refill Rate
1-700
1
(1)
gpm x 100
Used with salt amount to calculate refill time.
P15
Draw Rate
1-700
1
(1)
gpm x 100
Used with salt amount to calculate draw time.
P16
Flow sensor select
1-4
1
4
1 = 1" Autotrol turbine
2 = 2" Autotrol turbine
3 = User defined K-factor
4 = Fleck 3/4" Paddle
5 = Fleck 3/4" Turbine
6 = Fleck 1" Paddle
7 = Fleck 1"/1-1/2" Turbine
8 = Fleck 1-1/2" Paddle
9 = Meter Factor
P17
K-factor or Pulse
equivalent
0.01-99.99
0.01
0.01
K-factor P16 = 3;
Pulse Equivalent P16 = 9
P18
Tank in Service
1-2
1
1
Select the Tank in Service.
P19
Cleaning Cycle Interval
0-100
1
6
Number of standard regeneration cycles
between cleaning regeneration cycles.
*The controller will automatically adjust the Hardness Setting P8 when the sensors in the resin tank detect a hardness front passing. This
automatic adjustment to the hardness setting may result in the system passing hard water near the end of the service cycle if the resin tank
sensor placement setting P12 is wrong. The sensor placement setting P12 must be reduced to eliminate the problem. Reducing the Capacity
Setting P7 or increasing the Hardness setting P8 will only produce a temporary solution.
NOTE: (1) Default selected with initial setting value.
(2) Facotry Default is "0" for North America units and "1" for World units.
PROGRAMMING MODE continued