beautypg.com

Bryant Multipurpose Oil 369AAN User Manual

Page 6

background image

MASONRY CHIMNEYS

This furnace can be vented into an existing masonry chimney. This
furnace must not be vented into a chimney servicing a solid fuel
burning appliance. Before venting furnace into a chimney, the
chimney MUST be checked for deterioration and repaired if
necessary. The chimney must be properly lined and sized per local
or national codes.

If furnace is vented into a common chimney, the chimney must be
of sufficient area to accommodate the total flue products of all
appliances vented into chimney.

The following requirements are provided for a safe venting
system:

1. Be sure that chimney flue is clear of any dirt or debris.

2. Be sure that chimney is not servicing an open fireplace.

3. Never reduce pipe size below the outlet size of furnace.

(See Fig. 2.)

4. All pipe should be supported using proper clamps and/or

straps. These supports should be at least every 4 ft.

5. All horizontal runs of pipe should have at least 1/4-in. per

ft of upward slope.

6. All runs of pipe should be as short as possible with as few

turns as possible.

7. Seams should be tightly joined and checked for leaks.

8. The flue pipe must not extend into chimney but be flush

with inside wall.

9. The chimney must extend 3 ft above highest point where it

passes through the roof of a building and at least 2 ft higher
than any portion of a building within a horizontal distance
of 10 ft. It shall also be extended at least 5 ft above highest
connected equipment flue collar.

10. Check local codes for any variance.

FACTORY-BUILT CHIMNEYS

Listed factory-built chimneys may be used. Refer to chimney
manufacturer’s instructions for proper installation.

E.

Oil Burner

This furnace is supplied with a high-pressure atomizing retention
head-type burner (for use with grade 1 or 2 fuel oil). The mounting
flange is fixed to burner air tube and no adjustment is required for
insertion length.

F.

Oil Connections

Complete instructions for installing fuel oil piping can be found in
oil burner Installation Instructions included with furnace.

Oil line entry holes are provided in side panels. Two holes are
provided in each location so that a 2-pipe system may be used if
desired.

An oil filter should be used with all oil burners and should be
installed as close to burner as possible.

G.

Barometric Draft Control

The barometric draft control shipped with furnace MUST be used
with furnace to ensure proper operation. Instructions for installing
control are packed with control.

H.

Electrical Connections

WARNING:

The unit cabinet must have an uninter-

rupted or unbroken electrical ground to minimize per-
sonal injury if an electrical fault should occur. A green
ground screw is provided in control box for this connec-
tion.

115-V WIRING

Before proceeding with electrical connections, make certain that
voltage, frequency, and phase correspond to that specified on unit
rating plate. Also, check to be sure that service provided by utility
is sufficient to handle load imposed by this equipment. Refer to
rating plate or Table 7 for equipment electrical specifications.
Make all electrical connections in accordance with National
Electrical Code (NEC) ANSI/NFPA 70-2001 and any local codes
or ordinances that might apply. For Canadian installations, all
electrical connections must be made in accordance with Canadian
Electrical Code CSA C22.1 or subauthorities having jurisdiction.

CAUTION:

Do not connect aluminum wire between

disconnect switch and furnace. Use only copper wire.
Failure to follow this caution will lead to intermittent
electrical operation and/or fire hazard.

The control system depends on correct polarity of power supply.
Connect HOT wire (H) and NEUTRAL wire (N) as shown in Fig.
3 or 4.
A separate line voltage supply MUST be used with a fused
disconnect switch or circuit breaker between main power panel
and unit. (See Fig. 3 or 4.)
Metallic conduit (where required/used) may terminate at side panel
of unit. It is not necessary to extend conduit inside unit from side
panel to control box.
When replacing any original furnace wiring, use only 105°C No.
14 AWG copper wire.

24-V WIRING

Instructions for wiring thermostat (field supplied) are packed in
thermostat box. Make thermostat connections as shown in Fig. 3 or
4 at 24-v terminal board on fan timer board.

ACCESSORIES

When installing optional accessories to this appliance, follow
manufacturer’s Installation Instructions included with accessory.
Other than wiring for thermostat, wire with a minimum of type

T

insulation (63°F rise) must be used for accessories.

I.

Horizontal or Downflow Installation

For horizontal installation, determine which

side

will become the

top

, when the unit is laid down. Remove the flue pipe clearance

knock-out from the top of that side panel. Install the flue elbow so
that it exits the cabinet of the furnace through that opening.
For counterflow installation, the flue pipe must exit the cabinet
through 1 of the side panel openings (as above), then extended up
the side of the furnace. Insure that adequate clearances to com-
bustibles are observed. Downflow Conversion/Vent Guard Kit
MUST be used.

TABLE 7—ELECTRICAL DATA

UNIT

SIZE

VOLTS—
HERTZ—

PHASE—

OPERATING

VOLTAGE RANGE

MAX

UNIT

AMPS

MIN

WIRE

GAGE

MAX WIRE

LENGTH (FT)

MAX FUSE OR

CKT BKR AMPS

Max.*

Min.*

036105

115—60—1

132

104

12.2

14

26

15

060120

115—60—1

132

104

15.7

12

26

20

* Permissible limits of voltage range at which unit will operate satisfactorily.
† Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
‡ Time-delay fuse is recommended.

—6—