beautypg.com

Bryant Multipurpose Oil 369AAN User Manual

Page 5

background image

1. If combustion air is taken through a permanent opening

directly communicating with the outdoors, the opening shall
have a minimum free area of 1 sq in. per 4000 Btuh of total
input rating for all equipment in the enclosure.

2. If combustion air is taken from outdoors through vertical

ducts, the openings and ducts MUST have at least 1 sq in.
of free area per 4000 Btuh of the total input for all
equipment within the confined space. (See Table 5.)

3. If combustion air is taken from outdoors through horizontal

ducts, the openings and ducts MUST have at least 1 sq in.
of free area per 2000 Btuh of the total input for all
equipment within the confined space. (See Table 6.)

When ducts are used to supply air, they must be of the same cross
sectional area as free area of openings to which they connect.

The minimum dimension of rectangular air ducts must not be less
than 3 in.

C.

Duct Work Recommendations

WARNING:

When supply ducts carry air circulated by

furnace to areas outside spaces containing furnace, return
air MUST also be handled by a duct sealed to furnace
casing and terminating outside space containing furnace.
Incorrect duct work termination and sealing will create a
hazardous condition which could lead to bodily harm.

CAUTION:

Return-air grilles and warm air registers

MUST NOT be obstructed. Failure to follow this caution
will result in premature failure of heat exchanger.

The proper sizing of warm air ducts is necessary to ensure
satisfactory furnace operation. Duct work should be in accordance
with the latest editions of NFPA-90A (Installation of Air Condi-
tioning and Ventilating Systems) and NFPA-90B (Warm Air
Heating and Air Conditioning Systems) or Canadian equivalent.

The supply duct work should be attached to flanged front opening
provided at discharge end of furnace. The return-air duct work
should be attached to flanged rear opening of furnace. See Fig. 2
for dimensions of these openings.

NOTE:

The back (blower access opening) should not be used for

return air.

The following recommendations should be followed when install-
ing duct work:

1. Install locking-type dampers in all branches of individual

ducts to balance out system. Dampers should be adjusted to
impose proper static at outlet of furnace

2. A flexible duct connector of noncombustible material

should be installed at unit on both supply- and return-air
systems. In applications where extremely quiet operation is
necessary, the first 10 ft (if possible) of supply and return
ducts should be internally lined with acoustical material.

3. In cases where return-air grille is located close to fan inlet,

there should be at least one 90° air turn between fan inlet
and grille. Further reduction in sound level can be accom-
plished by installing acoustical air turning vanes or lining
duct as described in item 2 above.

4. When a single air grille is used, duct between grille and

furnace must be the same size as return opening in furnace.

D.

Venting

Venting of furnace should be to the outside and in accordance with
local codes or requirements of local utility.

OIL-FIRED APPLIANCES SHALL BE CONNECTED TO
FLUES HAVING SUFFICIENT DRAFT AT ALL TIMES TO
ENSURE SAFE AND PROPER OPERATION OF APPLIANCE.

For additional venting information, refer to ANSI/NFPA 211
Chimney, Fireplaces, Vents, and Solid Fuel Burning Appliances
and/or CSA B139 Installation Code.

This furnace is certified for use with Type

L

vent (maximum flue

gas temperature 575°F).

VENT SYSTEM INSPECTION

Before furnace is installed, it is highly recommended that any
existing vent system be completely inspected.

For any chimney or vent, this should include the following:

1. Inspection for any deterioration in chimney or vent. If

deterioration is discovered, chimney must be repaired or
vent must be replaced.

2. Inspection to ascertain that vent system is clear and free of

obstructions. Any blockage must be cleared before install-
ing furnace.

3. Cleaning chimney or vent if previously used for venting a

solid fuel burning appliance or fireplace.

4. Confirming that all unused chimney or vent connections are

properly sealed.

5. Verification that chimney is properly lined and sized per the

applicable codes. (Refer to list of codes in Safety Consid-
erations section.)

TABLE 4—COMBUSTION AIR

FROM UNCONFINED SPACE

369AAN FURNACE

INPUT BTUH

FREE AREA PER

OPENING

(SQ IN.)

70,000

100

91,000

100

105,000

105

119,000

119

140,000

140

154,000

154

TABLE 5—COMBUSTION AIR FROM OUTDOORS

THROUGH VERTICAL DUCTS

369AAN FURNACE

INPUT BTUH

FREE AREA PER

OPENING

(SQ IN.)

ROUND PIPE

(IN. DIAM)

70,000

17.5

5

91,000

22.8

6

105,000

26.3

6

119,000

29.8

6

140,000

35.0

6

154,000

38.5

6

TABLE 6—COMBUSTION AIR FROM OUTDOORS

THROUGH HORIZONTAL DUCTS

369AAN FURNACE

INPUT BTUH

FREE AREA PER OPENING

(SQ IN.)

ROUND PIPE

(IN. DIAM)

70,000

35.0

7

91,000

45.5

8

105,000

52.5

9

119,000

59.5

9

140,000

70.0

10

154,000

77.0

10

—5—