Ustang, Eries, Sizing – Watts M1110-14 User Manual
Page 3: Headloss

M
ustang
s
eries
12541 Gulf Freeway
•
Houston, Texas 77034
•
(Ph) 713.943.0688
•
(Fx) 713.944.9445
•
www.watts.com
Sizing
Size (in)
1-1/4
1-1/2
2
2-1/2
3
4
6
8
10
Maximum Continuous (GPM)
95
130
210
300
485
800
1850
3100
5000
Maximum Intermittent (GPM)
119
161
265
390
590
1000
2300
4000
6250
CV Factor GPM (Globe)
25
30
45
75
100
175
490
770
1200
CV Factor GPM (Angle)
26
27
57
91
125
215
571
990
1530
Maximum continuous flow based on velocity of 20 ft. per second.
Maximum intermittent flow based on velocity of 25 ft. per second.
2-1/2
4
10
6
8
2
3
12 14 16
2-1/2
4
10
6
8
2
3
12 14 16
1-1/4 1-1/2
1-1/4 1-1/2
Flow Rate - Gallons per minute
Pressure Drop (p.s.i.)
Angle
Globe
2 4 6 8
10
20
40
60 80 100 200 500 1000 2000 5000 10000 20000
100000
Maximum continuous flow based on velocity of 20 ft. per second.
Maximum intermittent flow based on velocity of 25 ft. per second.
The C
v
Factor of a value is the flow rate in US GPM at 60° F that will cause a 1 psi drop in pressure.
The factors stated are based upon a fully open valve.
Cv factor can be used in the following equations to determine Flow (Q) and Pressure Drop (∆ P):
Q (Flow) = C
v
∆ P ∆ P (Pressure Drop) = (Q/C
V
)
2
Headloss
NOTE: The above chart is a suggested guide. Inlet pressure, outlet pressure, minumum, normal and maximum flow rates should
be considered for specific valve sizing. Contact Watts ACV for details.
100
80
60
40
30
20
10
8
6
4
3
2
M110-14 (Globe)
M1110-14 (Angle)