Watts R24-12-1111000 User Manual
Page 5
![background image](/manuals/589287/5/background.png)
A. SPECIFICATIONS
R24-08 R24-10
R24-12
Maximum Productivity
(Gallons per day / Gallons per minute)
Maximum production based on standard membranes and feed water of
25°C, SDI < 3, 1000 ppm TDS, and pH 8. Individual membrane
productivity may vary (± 15%). May be operated on other feed waters
with reduced capacity.
14,400 / 10
18,000 / 12.5
21,600 / 15
Quality
(Typical Membrane Percent Rejection)
Based on membrane
manufactures specifications, overall system percent rejection may be less.
98 %
98 %
98 %
Recovery (without reject recirculation)
Recovery (with reject recirculation, depending on feed water)
59 %
75 %
59 %
75 %
59 %
75 %
Membrane Size
4 x 40
4 x 40
4 x 40
Number Of Membranes Per Vessel
2 2
2
Pressure Vessel Array
2:1:1 2:2:1
3:2:1
Number Of Membranes
8 10
12
Prefilter
(System ships with one 5 micron cartridge)
20" BB
20" BB
20" BB
Feed Water Connection
1 1/2" NPT
1 1/2" NPT
1 1/2" NPT
Product Water Connection
1" NPT
1" NPT
1" NPT
Reject Water Connection
3/4" NPT
3/4" NPT
3/4" NPT
Feed Water Required
Feed water required will be less if reject recycle is used.
17 gpm
21 gpm
25 gpm
Feed Water Pressure
(Minimum)
20 psi
20 psi
20 psi
Drain Required
17 gpm
21 gpm
25 gpm
Electrical Requirement
230 VAC, 3-ph, 60 Hz (Other voltages available)
15 amps
15 amps
15 amps
Grundfos Multistage Centrifugal Pump
(Model)
CRX4-160/14G CRX4-160/14G
CRX4-160/14G
TEFC Motor
(Horse Power)
5 5
5
Dimensions L x W x H
(Ft.)
8 x 3 x 6
8 x 3 x 6
8 x 3 x 6
Shipping Weight
(Estimated Pounds)
1000 1100
1200