Bryant DURAPAC PLUS 581A User Manual
Page 30
![background image](/manuals/58833/30/background.png)
—
30
—
Table 26 — Accessory/FIOP Static Pressure (in. wg)*
LEGEND
*The static pressure must be added to the external static pressure. The sum and the evaporator entering-air cfm should then be
used in conjunction with the Fan Performance tables to determine blower rpm and watts.
Table 27 — Fan Rpm at Motor Pulley Settings*
*Approximate fan rpm shown.
XII. OPTIONAL ECONOMI$ER IV
See Fig. 23 for EconoMi$er IV component locations. The
optional EconoMi$er IV comes from the factory fully wired
and assembled. No field wiring or assembly is required for
standard outdoor dry bulb changeover operation. Field wir-
ing of accessory sensors is required for different operational
modes.
A. EconoMi$er IV Standard Sensors
Outdoor Air Temperature (OAT) Sensor
The outdoor air temperature sensor (HH57AC074) is a 10 to
20 mA device used to measure the outdoor-air temperature.
The outdoor-air temperature is used to determine when the
EconoMi$er IV can be used for free cooling. The sensor is
factory-installed on the EconoMi$er IV in the outdoor air-
stream. See Fig. 23. The operating range of temperature
measurement is 40 to 100 F.
Supply-Air Temperature (SAT) Sensor
The supply-air temperature sensor is a 3 K thermistor
located at the outlet of the indoor fan. See Fig. 24. This sen-
sor is factory installed. The operating range of temperature
measurement is 0° to 158 F.
The temperature sensor is a short probe with blue wires
running to it.
Outdoor Air Lockout Sensor
The EconoMi$er IV is equipped with an ambient tempera-
ture lockout switch located in the outdoor airstream which is
used to lock out the compressors below a 42 F ambient
temperature.
B. EconoMi$er IV Controller Wiring and Operational Modes
Determine the EconoMi$er IV control mode before set up of the
control. Some modes of operation may require different sensors.
Refer to Table 28. The EconoMi$er IV is supplied from the
factory with a supply-air temperature sensor and an
outdoor air temperature sensor. This allows for operation of
the EconoMi$er IV with outdoor air dry bulb changeover
control. Additional accessories can be added to allow for dif-
ferent types of changeover control and operation of the
EconoMi$er IV and unit.
Outdoor Dry Bulb Changeover
The standard controller is shipped from the factory config-
ured for outdoor dry bulb changeover control. The outdoor
air and supply-air temperature sensors are included as
standard. For this control mode, the outdoor temperature is
compared to an adjustable set point selected on the control.
If the outdoor-air temperature is above the set point, the
EconoMi$er IV will adjust the outdoor-air dampers to mini-
mum position. If the outdoor-air temperature is below the set
point, the position of the outdoor-air dampers will be con-
trolled to provide free cooling using outdoor air. When in this
mode, the LED next to the free cooling set point potentiome-
ter will be on. The changeover temperature set point is con-
trolled by the free cooling set point potentiometer located on
the control. The scale on the potentiometer is A, B, C, and D.
See Fig. 25 for the corresponding temperature changeover
values.
COMPONENT
CFM
4,000
4,500
5,000
5,500
6,000
6,500
7,000
7,500
8,000
8,500
9,000
9,500
10,000
10,500
11,000
11,500
12,000
EconoMi$er IV
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.13
0.15
0.16
0.17
0.19
0.20
FIOP
—
Factory-Installed Option
581A
UNIT
SIZE
DRIVE
MOTOR PULLEY TURNS OPEN
0
1
/
2
1
1
1
/
2
2
2
1
/
2
3
3
1
/
2
4
4
1
/
2
5
5
1
/
2
6
210
(208/230 and
460 volt)
Low Range Vertical
647
667
687
707
727
747
767
786
806
826
846
866
886
High Range Vertical
897
917
937
958
978
998
1018
1038
1058
1079
1099
1119
1139
Low Range Horizontal
896
924
951
979
1006
1034
1062
1089
1117
1144
1172
1199
1227
High Range Horizontal
1113
1138
1163
1188
1213
1238
1264
1289
1314
1339
1364
1389
1414
210
(575 volt)
Low Range Vertical
810
832
854
876
897
919
941
963
985
1007
1028
1050
1072
High Range Vertical
873
893
912
932
951
971
991
1010
1030
1049
1069
1088
1108
Low Range Horizontal
863
886
909
933
956
979
1002
1025
1048
1072
1095
1118
1141
High Range Horizontal
1042
1062
1083
1103
1123
1143
1164
1184
1204
1224
1245
1265
1285
240
(208/230 and
460 volt)
Low Range Vertical
949
970
992
1013
1035
1056
1078
1099
1120
1142
1163
1185
1206
High Range Vertical
941
961
980
1000
1019
1039
1059
1078
1098
1117
1137
1156
1176
Low Range Horizontal
1113
1138
1163
1188
1213
1238
1264
1289
1314
1339
1364
1389
1414
High Range Horizontal
1096
1116
1137
1157
1177
1197
1218
1238
1258
1278
1299
1319
1339
240
(575 volt)
Low Range Vertical
949
970
992
1013
1035
1056
1078
1099
1120
1142
1163
1185
1206
High Range Vertical
941
961
980
1000
1019
1039
1059
1078
1098
1117
1137
1156
1176
Low Range Horizontal
1113
1138
1163
1188
1213
1238
1264
1289
1314
1339
1364
1389
1414
High Range Horizontal
1096
1116
1137
1157
1177
1197
1218
1238
1258
1278
1299
1319
1339
300
(all voltages)
Low Range Vertical
941
961
980
1000
1019
1039
1059
1078
1098
1117
1137
1156
1176
High Range Vertical
1014
1038
1061
1085
1108
1132
1156
1179
1203
1226
1250
1273
1297
Low Range Horizontal
941
961
980
1000
1019
1039
1059
1078
1098
1117
1137
1156
1176
High Range Horizontal
1014
1038
1061
1085
1108
1132
1156
1179
1203
1226
1250
1273
1297