Table 4A — Electrical Data — Units Without Convenience Outlet

LEGEND

*Fuse or HACR circuit breaker.

NOTES:

1. In compliance with NEC requirements for multimotor and combination load equip-

ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than
2%. Use the following formula to determine the percent voltage imbalance.

Determine maximum deviation from average voltage.

(AB) 457 - 452 = 5 v
(BC) 464 - 457 = 7 v
(AC) 457 - 455 = 2 v

Maximum deviation is 7 v.
Determine percent voltage imbalance.

This amount of phase imbalance is satisfactory as it is below the maximum allow-
able 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact the
local electric utility company immediately.

3. The convenience outlet full load amps (FLA) are 5, 3, and 3 for 208/230, 460,

575-V units, respectively.

581A
UNIT

SIZE

NOMINAL

VOLTAGE

(3 Ph,

60 Hz)

VOLTAGE

RANGE

COMPRESSOR

OFM

IFM

POWER

EXHAUST

COMBUSTION

FAN MOTOR

POWER SUPPLY

DISCONNECT

SIZE

No. 1

No. 2

No. 3

Min

Max

RLA

LRA

RLA

LRA

RLA

LRA

Qty

Hp

FLA

(ea)

Hp

FLA

Qty Hp

FLA

(ea)

FLA

MCA

MOCP*

FLA

210

208/230

187

253

16.7

130

16.7

130

22.4

184

4

0.25

1.5

3.7

10.6/ 9.6

0.5

78/ 77

100/ 90

83/ 82

2

1

5.9

90/ 89

100/100

97/ 96

5

16.7/15.2

84/ 83

100/100

90/ 89

2

1

5.9

96/ 94

100/100

104/102

460

414

506

9

70

9

70

10.7

90

4

0.25

0.7

3.7

4.8

0.3

39

45

42

2

1

3.1

45

50

49

5

7.6

42

50

45

2

1

3.1

48

50

52

575

518

633

7

55

7

55

9.3

73

4

0.25

0.7

3

3.9

0.24

32

40

35

2

1

2.4

37

45

40

5

6.1

35

40

37

2

1

2.4

39

45

43

240

208/230

187

253

22.4

184

22.4

184

22.4

184

4

0.25

1.5

5

16.7/15.2

0.5

96/ 94

100/100

103/102

2

1

5.9

107/106 125/125

117/115

7.5

24.2/22

103/101 125/110

112/109

2

1

5.9

115/113 125/125

126/123

460

414

506

10.7

90

10.7

90

10.7

90

4

0.25

0.7

5

7.6

0.3

45

50

49

2

1

3.1

51

60

56

7.5

11

49

50

53

2

1

3.1

55

60

60

575

518

633

9.3

73

9.3

73

9.3

73

4

0.25

0.7

5

6.1

0.24

39

45

42

2

1

2.4

44

50

48

7.5

9

42

50

46

2

1

2.4

47

50

51

300

208/230

187

253

47.1

245

47.1

245

6

0.25

1.5

7.5

24.2/22

0.5

139/137 175/175

147/144

2

1

5.9

151/149 175/175

160/158

10

30.8/28

146/143 175/175

154/151

2

1

5.9

158/155 200/200

168/164

460

414

506

19.6

125

19.6

125

6

0.25

0.7

7.5

11

0.3

59

60

63

2

1

3.1

66

80

70

10

14

62

80

66

2

1

3.1

69

80

73

575

518

633

15.8

100

15.8

100

6

0.25

0.7

7.5

9

0.24

49

60

52

2

1

2.4

54

60

57

10

11

51

60

54

2

1

2.4

56

60

59

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage

EXAMPLE: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

Average Voltage =

452 + 464 + 455

3

=

1371
3

= 457

% Voltage Imbalance = 100 x

7

457

= 1.53%