VIII. CONDENSER FANS AND MOTORS
Condenser fans and motors are factory set. Refer to
Condenser-Fan Adjustment section (page 39) as required.
IX. RETURN-AIR FILTERS
Check that correct filters are installed in filter tracks (see
Table 1). Do not operate unit without return-air filters.
NOTE: For units with 4-in. filter option, units are shipped
with standard 2-in. filters. To install 4-in. filters, the filter
spacers must be removed.
X. OUTDOOR-AIR INLET SCREENS
Outdoor-air inlet screens must be in place before operating
unit.
XI. GAS HEAT
Verify gas pressures before turning on heat as follows:
1. Turn off field-supplied manual gas stop, located
external to unit.
2. Connect pressure gage to supply gas tap, located on
field-supplied manual shutoff valve (see Fig. 14).
3. Connect pressure gage to manifold pressure tap.
4. Turn on field-supplied manual gas stop. Provide a
call for heating stage 1.
5. After the unit has run for several minutes, verify
the supply gas pressure is between 5.5 in. wg and
13.0 in. wg. Provide a call for heating stage 2. Check
manifold pressure after 5 minutes of stage 2 opera-
tion. Manifold pressure should be 3.00 in. wg. If
manifold pressure must be adjusted, refer to Gas
Valve Adjustment section.
NOTE: Supply gas pressure must not exceed
13.0 in. wg.
6. Turn off unit.
7. Remove call for heat.
Table 5 — Fan Performance — 581A210 Low Heat Vertical Discharge Units*
LEGEND
*Motor drive ranges:
Low Range: 647-886 (208/230 and 460-v), 810-1072 (575-v)
High Range: 897-1139 (208/230 and 460-v), 873-1108 (575-v)
All other rpms require field-supplied drive.
Refer to page 23 for general Fan Performance Data notes.
NOTE: Maximum continuous bhp is:
Low Range: 4.25 (208/230 and 460-v), 3.45 (575-v)
High Range: 5.75
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
3500
460
591
0.68
548
774
0.89
623
951
1.09
692
1126
1.29
755
1301
1.50
4000
499
774
0.89
581
976
1.12
653
1170
1.35
717
1361
1.56
777
1551
1.78
4500
538
990
1.14
617
1212
1.39
685
1423
1.64
746
1630
1.88
803
1835
2.11
5000
579
1243
1.43
654
1485
1.71
719
1715
1.97
778
1938
2.23
832
2158
2.48
5500
621
1536
1.77
693
1798
2.07
755
2045
2.35
811
2285
2.63
864
2520
2.90
6000
664
1871
2.15
732
2152
2.48
792
2417
2.78
846
2673
3.07
897
2925
3.36
6500
707
2250
2.59
772
2550
2.93
830
2834
3.26
883
3106
3.57
932
3373
3.88
7000
751
2676
3.08
813
2994
3.44
869
3295
3.79
920
3585
4.12
967
3868
4.45
7500
795
3150
3.62
855
3487
4.01
909
3805
4.38
958
4112
4.73
1004
4411
5.07
8000
839
3676
4.23
897
4029
4.63
949
4366
5.02
997
4689
5.39
1042
5004
5.75
8500
884
4253
4.89
940
4625
5.32
990
4978
5.73
1037
5318
6.12
1080
5649
6.50
AIRFLOW
(Cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
3500
814
1476
1.70
871
1650
1.90
924
1825
2.10
975
1999
2.30
1023
2173
2.50
4000
834
1740
2.00
888
1930
2.22
939
2119
2.44
988
2308
2.65
1035
2497
2.87
4500
857
2039
2.35
909
2243
2.58
958
2446
2.81
1005
2650
3.05
1051
2853
3.28
5000
884
2376
2.73
933
2594
2.98
980
2811
3.23
1026
3028
3.48
1070
3244
3.73
5500
913
2753
3.17
960
2984
3.43
1006
3215
3.70
1049
3445
3.96
1092
3674
4.23
6000
945
3172
3.65
990
3417
3.93
1034
3662
4.21
1076
3905
4.49
1117
4147
4.77
6500
978
3636
4.18
1022
3895
4.48
1064
4153
4.78
1104
4409
5.07
1144
4665
5.37
7000
1012
4145
4.77
1055
4419
5.08
1095
4691
5.39
1135
4960
5.70
1173
5229
6.01
7500
1047
4703
5.41
1089
4992
5.74
1128
5277
6.07
1167
5561
6.40
1204
5842
6.72
8000
1084
5311
6.11
1124
5615
6.46
1163
5915
6.80
1200
6211
7.14
1236
6506
7.48
8500
1121
5972
6.87
1160
6290
7.23
1198
6604
7.60
1234
6914
7.95
1269
7223
8.31
Bhp
—
Brake Horsepower Input to Fan
Watts
—
Input Watts to Motor