Q45UML
Transferring Window Limit Settings from the Q45UML to a Sensor
Use the following procedure to copy sensing window limit settings stored on a
Q45UML card to a Q45U sensor:
1)
Remove power from the Q45U sensor.
2)
Remove the output card from the Q45U sensor (Figure 1). Use a small
screwdriver, or similar tool, to dislodge the output card from its connector. Then,
slide the card out of the sensor.
3)
Check to be certain that Switch #1 on the Q45UML card is set to “on”
(see Figure 2).
4) Slide the Q45UML card into the sensor in place of the sensor output card
(Figure 3). Push it firmly into place.
5) Apply power to the sensor. The window limits are copied from the Q45UML card
when power is applied to the sensor. The outermost two segments of the 5-
segment LED indicator on the Q45UML will flash simultaneously to verify that the
limit settings have been copied to the sensor.
6) Remove power from the Q45U sensor.
7) Remove the Q45UML card in the same manner used to remove the output card in
step 2 (Figure 1).
8) Slide the output card back into the Q45U sensor, and push firmly into place.