Physical data, 213r – Bryant LEGACY 213R User Manual

Page 3

background image

3

PHYSICAL DATA

UNIT SIZE --- SERIES

018---A

024---A

030---A

036---A

042---A

048---A

060---A

Operating Weight (lb)

159

160

208

211

233

269

295

Shipping Weight (lb)

184

185

240

242

262

300

327

Compressor Type

Scroll

REFRIGERANT

Freon® (R---22)

Control

TXV (R---22 Hard Shutoff)

Charge (lb)

5.5

6

7.5

8

10

14

15.5

COND FAN

Propeller Type, Direct Drive

Air Discharge

Vertical

Air Qty. (CFM)

2233

2614

2614

3334

3334

4046

4046

Motor HP

1/12

1/10

1/10

1/8

1/8

1/5

1/5

Motor RPM

800

1100

1100

800

800

800

800

COND COIL

Face Area (Sq. ft.)

15.09

15.09

25.87

22.63

17.6

22.63

25.15

Fins per In.

20

20

20

20

20

20

20

Rows

1

1

1

1

2

2

2

Circuits

5

6

6

6

7

8

9

VALVE CONNECT. (In. ID)

Vapor

5/8”

5/8”

3/4”

3/4”

7/8”

7/8”

7/8”

Liquid

3/8”

REFRIGERANT TUBES* (In. OD)

Vapor (0---80 Ft. Tube Length)

5/8”

5/8”

3/4”

3/4”

7/8”

7/8”

1---1/8”

Liquid (0---80 Ft. Tube Length)

3/8”

* For tubing sets between 80 and 200 ft. horizontal or 20 ft. vertical differential, consult the Longline Guideline.

Note: See unit Installation Instruction for proper installation.

VAPOR LINE SIZING AND COOLING CAPACITY LOSS

1--STAGE HEAT PUMP APPLICATIONS

LONG LINE APPLICATION: An application is considered
”Long line” when the total equivalent tubing length exceeds 80

ft. or when there is more than 20 Ft. vertical separation between
indoor and outdoor units. These applications require additional

accessories and system modifications for reliable system

operation. The maximum allowable total equivalent length is 250
ft. The maximum vertical separation is 200 ft. when outdoor unit

is above indoor unit, and 60 ft. when the outdoor unit is below
the indoor unit. Refer to Accessory Usage Guideline below for

required accessories. See Long--Line Application Guideline for
required piping and system modifications. Also, refer to the table

below for the acceptable vapor tube diameters based on the total

length to minimize the cooling capacity loss.

Unit Nominal Size (Btuh)

Acceptable Vapor

Line Diameter OD

(in.)

Cooling Capacity Loss (%)

Total Equivalent Line Length (ft.)

Standard Application

Long Line Application

Requires Accessories

25

50

80

80+

100

125

150

175

200

225

250

18000

R---22 HP

5/8

0

1

1

1

2

3

3

4

5

5

6

3/4

0

0

0

0

0

1

1

1

1

2

2

24000

R---22 HP

5/8

0

1

3

3

3

5

6

7

8

9

10

3/4

0

0

0

0

1

1

1

2

2

3

3

30000

R---22 HP

3/4

0

1

1

1

2

3

3

4

5

5

6

7/8

0

0

0

0

1

1

1

2

2

2

3

36000

R---22 HP

3/4

0

1

2

2

3

4

5

6

7

8

9

7/8

0

0

1

1

1

2

2

3

3

4

4

42000

R---22 HP

7/8

0

1

1

1

2

2

3

4

4

5

5

48000

R---22 HP

7/8

0

1

2

2

2

3

4

5

5

6

7

60000

R---22 HP

7/8

1

2

3

3

4

5

7

8

9

10

11

1 1/8

0

0

1

1

1

1

2

2

2

3

3

Standard Length = 80 ft. or less total equivalent length

Applications in this area are long line. Accessories are required as shown recommended on Long Line Application Guidelines

Applications in this area may have height restrictions that limit allowable total equivalent length, when outdoor unit is below indoor unit See

Long Line Application Guidelines

213R