Detailed cooling capacities -- continued, 213r – Bryant LEGACY 213R User Manual

Page 24

background image

24

DETAILED COOLING CAPACITIES -- CONTINUED

EVAPORATOR

AIR

CONDENSER ENTERING AIR TEMPERATURES deg F

75

85

95

105

115

125

CFM

EWB

Capacity

MBtuh†

Total

System

KW**

Capacity

MBtuh†

Total

System

KW**

Capacity

MBtuh†

Total

System

KW**

Capacity

MBtuh†

Total

System

KW**

Capacity

MBtuh†

Total

System

KW**

Capacity

MBtuh†

Total

System

KW**

Total

Sens

Total

Sens

Total

Sens

Total

Sens

Total

Sens

Total

Sens

213RNA060---A Outdoor Section With FC4DNF060 Indoor Section

1750

72

69.61 35.82

4.46

67.00 34.80

4.88

64.31 33.76

5.34

61.53 32.71

5.85

58.62 31.62

6.41

55.59 30.48

7.02

67

63.45 44.44

4.39

61.04 43.40

4.81

58.55 42.34

5.27

55.98 41.25

5.78

53.30 40.13

6.33

50.49 38.96

6.93

63

58.99 42.98

4.34

56.74 41.94

4.76

54.40 40.87

5.21

51.98 39.77

5.72

49.46 38.64

6.27

46.83 37.46

6.87

62

57.89 52.98

4.33

55.72 51.90

4.74

53.47 50.76

5.20

51.16 49.56

5.71

48.78 48.25

6.26

46.47 46.47

6.87

57

56.07 56.07

4.31

54.33 54.33

4.73

52.50 52.50

5.19

50.59 50.59

5.70

48.58 48.58

6.26

46.47 46.47

6.87

2000

72

70.84 37.47

4.56

68.11 36.44

4.98

65.32 35.40

5.44

62.44 34.33

5.95

59.43 33.22

6.51

56.30 32.08

7.12

67

64.59 47.19

4.49

62.08 46.14

4.91

59.50 45.06

5.36

56.84 43.96

5.87

54.05 42.81

6.43

51.16 41.61

7.03

63

60.09 45.56

4.44

57.75 44.51

4.85

55.31 43.42

5.31

52.80 42.30

5.82

50.19 41.14

6.37

47.48 39.94

6.97

62

59.16 56.66

4.43

56.93 55.47

4.84

54.66 54.15

5.30

52.43 52.43

5.81

50.30 50.30

6.37

48.06 48.06

6.98

57

58.28 58.28

4.42

56.43 56.43

4.84

54.48 54.48

5.30

52.44 52.44

5.81

50.31 50.31

6.37

48.06 48.06

6.98

2250

72

71.75 39.04

4.66

68.93 38.00

5.07

66.06 36.95

5.53

63.10 35.87

6.05

60.01 34.75

6.61

56.79 33.60

7.21

67

65.44 49.83

4.58

62.86 48.76

5.00

60.20 47.66

5.46

57.46 46.53

5.97

54.61 45.35

6.52

51.65 44.13

7.13

63

60.91 48.02

4.53

58.49 46.94

4.95

55.99 45.83

5.40

53.41 44.69

5.91

50.74 43.50

6.46

47.96 42.27

7.06

62

60.29 59.79

4.53

58.14 58.14

4.94

56.08 56.08

5.41

53.95 53.95

5.92

51.71 51.71

6.48

49.36 49.36

7.09

57

60.11 60.11

4.53

58.14 58.14

4.94

56.09 56.09

5.41

53.95 53.95

5.92

51.72 51.72

6.48

49.36 49.36

7.09

Cooling Indoor Model

Capacity

Power

Furnace Model

*FC4DN(F,B)060

1.00

1.00

FK4DNB006

0.98

0.97

CAR**6024A**

0.97

0.97

315(A,J)AV066135

CSRH*6012A**

0.97

0.97

315(A,J)AV066135

CAR**6024A**

0.97

0.97

315(A,J)AV066155

CNRH*6024A**

0.97

0.97

315(A,J)AV066155

CNRV*6024A**

0.97

0.97

315(A,J)AV066155

CSRH*6012A**

0.97

0.97

315(A,J)AV066155

NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240---94. If additional tubing length and/or

indoor unit is located above outdoor unit, a slight variation in capacity may occur.

{

Total and sensible capacities are net capacities. Blower motor heat has been subtracted.

}

Sensible capacities shown are based on 80_F (27_C) entering air at the indoor coil. For sensible capacities at other than 80_F (27_C), deduct 835 Btuh

(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80_F (27_C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air

per degree above 80_F (27_C).

** System kw is total of indoor and outdoor unit kilowatts.
{{

At TVA rating indoor condition (75_F edb/63_F ewb). All other indoor air temperatures are at 80_F edb.

EWB — Entering Wet Bulb