beautypg.com

Vicor Constant Current (CC) Demonstration Board User Manual

Page 9

background image

UG:007

vicorpower.com

Applications Engineering: 800 927.9474

Page 9

6.

Verify proper power supply to CC board connections.

7.

Connect DMM to measure the output voltage using the output Kelvin test points.

8.

Turn V

REF

(R10) potentiometer clockwise gently until it reaches its maximum value of

100 K which corresponds to

≈ 5 V depending on its tolerance. The potentiometer has

stops which indicate that it has been turned fully in one direction. Do not wind the
potentiometer past the stop, as this may damage the part.

9.

Turn V

MAX

(R8) potentiometer counterclockwise gently until it reaches its maximum value

of 5 K which corresponds to an output voltage of

≈ 30 V depending on its tolerance.

The potentiometer has stops which indicate that it has been turned fully clockwise /
counterclockwise. Do not wind the potentiometer past the stop as this may damage the part.

10. Connect DMM to measure V

REF

at TP5 with reference to SG at TP6.

11. Make sure (SW02) is in "close" position.

12. Turn on a fan if desired.

13. Raise the DC input voltage to the nominal value of 48 V as indicated on the

PRM

P048F048T24AL datasheet

. The output voltage should read approximately 30 V if the

potentiometer has been turned fully counterclockwise as directed in step 9.

14. Set the load in constant current mode to 50% of the PRM’s rated output (2.5 A for the

P048F048T24AL-CC). With the load in this setting, the circuit will have no control and will
drive the PRM to its maximum value provided that the load current is less than the
reference set point. This allows for adjusting the maximum PRM output voltage.

15. Turn the potentiometer (R8) clockwise to set the maximum PRM output voltage. When

setting the maximum PRM output, keep in mind that the CC feedback can drive the
output voltage up to this maximum limit in order to maintain the required current. Due to
component tolerances, turning (R8) fully clockwise can result in the circuit driving the PRM
above its maximum voltage. If this is done with no load, the PRM may be damaged.
Do not set the maximum PRM voltage above 55 V.

16. Turn off the electronic load

17. Turn the potentiometer V

REF

(R10) counterclockwise to lower the PRM output current set

point to the desired value. If V

REF

is not lowered to a reasonable value below the DC

current limit, the PRM will start in a fault condition when connected to a load. It will
remain in fault until the potentiometer V

REF

(R10) is turned counterclockwise to lower the

set reference. An undesirable clicking sound will be audible in this case. Although
continuous operation in this mode will not damage the unit, it is not recommended.

18. Decrease the input voltage to low line.

You have now verified the operation of the CC and set the desired output current and
maximum output voltage.