P33CE Direct Vent Gas Fireplace

11

INSTALLATION

COMBUSTIBLE MANTELS

Because of the extreme heat this fi replace emits, the mantel clearances are critical. Combustible mantel clearances from top of unit are shown in the
diagram below.

Note: A non-combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non-combustible board.
This drawing is to scale at 1:6 (one inch = 6 inches). Mantel can be installed anywhere in shaded area or higher using the above scale.

Note: Ensure the paint that is used on the mantel and the facing is "heat resistant" or the paint may discolour.

Combustible mantel leg clearances as per diagrams below:

Drywall

Mantel Clearances

2

0

12

6

4

8

10

2

0

12

6

4

8

10

Top opening
of Unit

12" (305mm)

0” - 3-1/2" (89mm)

7-1/2"(191mm)

15-3/4" (400mm)

11-3/4"(298mm)

13-3/4"(349mm)

24-1/4"(616mm)

to floor

3"(76mm)

Standoff

Side View

16

14

Non-combustible material