beautypg.com

Troubleshooting guide – Schwank bistroSchwank 2-Stage User Manual

Page 36

background image

2100 / IO 100 Manual

IM110107

RD: MAY 2014

R.L. 4A

36

19. TROUBLESHOOTING GUIDE

TURN HEATER ON

24 VOLTS ±10% TO DSI CONTROL

24 VOLTS OUT FROM CONTROL

24 VOLTS AT GAS CONTROL

SPARK ACROSS IGNITER:
IS HIGH VOLTAGE SPARK OK ?

MAKE SURE THE MANUAL
SWITCH ON THE GAS VALVE IS
‘OPEN’ AND THAT THERE IS GAS
SUPPLY TO THE VALVE.

*CHECK 120 V AT PRIMARY TRANSFORMER

*CHECK VOLTAGE OUT AT SECONDARY.

*IF THERE IS NOT 24V TO SECONDARY....
.......REPLACE THE TRANSFORMER

*ENSURE GAS IS TURNED ON AT VALVE.

*CHECK ELECTRICAL CONNECTIONS AT

CONTROL & GAS VALVE.
*CHECK 24V WIRING CONTINUITY FROM DSI

IGNITION CONTROL TO GAS VALVE, RE-
PLACE WIRES IF NECESSARY.

*PERFORM IGNITION LEAD TEST DESCRIBED

IN “SPARK IGNITION CIRCUIT”.

*CHECK DSI MODULE IGNITION POST FOR
DEFECTS.

*SPARK IGNITER MAY BE OUT OF POSITION.
*CHECK BOOT OF THE IGNITION CABLE FOR

SIGNS OF MELTING OR BUCKLING. TAKE
PROTECTIVE ACTION TO SHIELD CABLE &

BOOT FROM EXCESSIVE TEMPERATURES.
*CHECK CERAMIC INSULATOR FOR CRACKS *

*CHECK SPARK GAP, 1/8”-3/16” .
*CHECK IGNITION CABLE, AND GROUND

WIRE

*CHECK 24V WIRING FROM TRANSFORMER

TO IGNITION CONTROL / AND CHECK IF

CORRECT GAUGE OF WIRE FOR DISTANCE.
*REPLACE WIRES IF NECESSARY.

*CHECK FOR 24 VAC ACROSS GAS VALVE

TERMINALS ON CONTROL. IF NO VOLTAGE,

.........REPLACE CONTROL.

YES

NO

NO

YES

YES

YES

YES

YES

NO

NO

NO

IF 24V IS PRESENT AND VALVE DOES NOT

OPEN.......REPLACE VALVE

GAS VALVE OPENS.

NO

This manual is related to the following products: