Warning – Schwank P40U Fenwal User Manual
Page 35
35
P40U-F / P40U-IF I&O Manual
IM101220
RD: MAY 2014
RL: 5A
24. TROUBLESHOOTING GUIDE — HEATER OPERATION — FENWAL DSI
Improper adjustment, alteration, service or maintenance can
cause property damage, injury or death. This heater must be
installed and serviced only by a trained gas service technician
SET THERMOSTAT TO CALL FOR
APPLY 120 VOLTS - GREEN LIGHT
CHECK 120V TO DSI AT “L1”
CHECK 120V OUT AT “IND” FROM DSI TO
COMBUSTION AIR BLOWER
AIR PROVING SWITCH HAS
CLOSED 24 VOLTS IS PRESENT
AT “PSW” AT DSI CONTROL.
CHECK TUBING TO SWITCH IS CON-
NECTED AND NOT BLOCKED OR KINKED
CHECK AIR PRESSURE WITH MANOME-
TER
CHECK FOR OBSTRUCTION IN THE AIR
INTAKE
CHECK DSI CONTROL FUSE FOR CONTI-
NUITY
VISIBLY CHECK IF IGNITER IS SHORTING
OUT
CHECK GROUND WIRING
REMOVE AND INSPECT IGNITER AND
LEAD
CHECK BOOT OF THE IGNITION CABLE
FOR SIGNS OF MELTING OR OVERHEAT-
ING
IF “YES” ... TAKE PROTECTIVE ACTION TO
SHIELD CABLE AND BOOT FROM EXCES-
SIVE TEMPERATURE; REPLACE ANY DE-
FECTIVE COMPONENT
SPARK IGNITER / SENSOR
24V TO GAS VALVE - RED LIGHT
CONTINUED
SEQUENCE OF EVENTS (also see DSI Troubleshooting previous page)
NO
YES
YES
YES
NO
NO
REMEDY 120 VOLTS SUPPLY FAULT
NO
NO
FAULTY RELAY SWITCH IN DSI — RE-
PLACE DSI
BLOCKED FLUE SWITCH IS
CLOSED
24 VOLTS IS PRESENT AT “TH” AT
YES
NO
CHECK TUBING TO SWITCH IS CON-
NECTED AND NOT BLOCKED OR KINKED
CHECK AIR PRESSURE WITH MANOME-
TER
CHECK INTEGRITY OF SWITCH
REPLACE DEFECTIVE SWITCH
WARNING