UHE-F / EIH-F I&O Manual

IM100205

RD: MAY 2014

RL: 06A

V

ERTICAL

VENT

THROUGH

THE

ROOF

:

It is the sole responsibility of the installer to
adhere to all current local codes and/or ANSI
Z223.1 / CSA.B149.1 latest editions for all
venting requirements, and practices.



Use an approved ‘B-vent’ termination cap
as supplied by the manufacturer of the ap-
proved ‘B-vent’.



When vent and combustion air are taken
through the roof, the exhaust vent should
always terminate higher than the combus-
tion air intake, to prevent recycling the
products of combustion back into the
heater



At most a quantity of three 90° elbows can be installed in a vertical vent

Approved
Cap

A p p r o v e d
‘B’ Vent

24”
60 cm

12

9

If roof slope exceeds 9:12
consult NFPA-54 ANSI
Z223.1 or CSA-B149.1

FIGURE 17

Up
to

Input

(Btuh)

Do Not Exceed

Maximum

Combined

System Length

Max. Air Duct

Length (ft)

(by Duct Diameter)

Max. Vent

Length (ft)

Individual: 4ӯ

Combined: 6ӯ

4”

Air Duct 5” Air Duct

4”

Ш / 5”

Ш

60,000

60 ft

80 ft

30 / 50

30

90,000

80 ft

100 ft

30 / 50

40

130,000

100 ft

120 ft

30 / 50

40

160,000

100 ft

120 ft

30 / 50

40

200,000

120 ft

140 ft

30 / 50

50

Example

160,000 Btuh Heater:

Tube Heater Length

50 ft

1 x 90° elbow (vent)

5 ft

Straight vent

20 ft

1 x 90° elbow (duct)

5 ft

Air Duct: 4” Ø

17 ft

Combined Length

97 ft

Max. Allowed

100 ft

Additional 20’ for 5” Ø Air Duct

11A. Combined System Length: Tube Heater + Vent + Combustion Air Duct

:

MINIMUM VENT LENGTH: (Vented or Unvented [indirect mechanical ventilation])



Minimum vent length of 3 ft (91 cm) is required

MAXIMUM SYSTEM LENGTH (includes:

Tube Heater length + combustion air duct +

vent

):



Each 90° elbow in the system has an equivalent length of 5 ft.



A maximum of 2 elbows are allowed in any portion (duct, tube heater, vent) with the ex-
ception of up to three 90° elbows in a vertical vent run through the roof



Combustion air duct may be 4” or 5” diameter and is not to exceed lengths in table below

 Exceeding the allowable lengths in the table below can create combustion and/or conden-

sation problems and will void CSA Certification and the heater warranty.

 Do not exceed the Maximum Combined System Length regardless of the allowed maximum

length of individual vent or combustion air duct