SATEC SLC500 User Manual
Page 22
![background image](/manuals/572150/22/background.png)
22
C.2.2 RS-422 Connection with Surge Voltage Protection
TxD
RxD
TxD-
RxD-
TxD
RxD
6
7
6
2
1
9
RxD'
TxD'
1746-BAS BASIC module
DB9 male connector
DB9 female connector
2
3
Series PM-280/288/270/290
Powermeters
RxD-
TxD-
RxD
TxD
6
7
DB9 male connector
RxD-
TxD-
RxD
TxD
Series PM-290H Powermeters
Series PM-170 Powermeters
8
9
14
15
16
17
DB25 male connector
5
1
1
1
GND
GND
GND
* A termination resistor should only be connected at the furthest end of the cable
COM
Z1
Z2
Z3
Z4
Z5
Z6
Z7
Z8
R3
R4
R5
Ω
Z1,Z3,Z5,Z7 - 1N4736A
Z2,Z4,Z6,Z8 - 1N4728A
*R2
R1
R6
**R7
**R8
R1,R2 - 120
R3,R4,R5,R6 - 33
R7,R8 - 1.2 k
Ω
Ω
** In RS-422 communication, a reference or common line should be used in addition to signal lines
use a reference line, place pull-down resistors R7 and R8 on both outputs of the driver to avoid
leaving the line floating when the line is idle
for stable operation. Connect pin 1 of the instruments with pin 5 on the BASIC module. If you don't