APPENDIX A DATA SETS
Table A-1 Data set #1
Field Field Name
CPU M1 file word
Units
Value evaluation
Range
No.
LO
HI
SIGN
formula
1
Instrument address
1
LO
1 - 31
2
Voltage A
2
3
V
3
Voltage B
4
5
V
HI*10000+LO
0 - 999,000
4
Voltage C
6
7
V
5
Current A
8
A
6
Current B
9
A
LO
0 - 32767
7
Current C
10
A
8
Active Power A
11
12
13
kW
HI*10000+LO
9
Active Power B
14
15
16
kW
SIGN = 0 means '+'
±
0 - 5,184,000
10
Active Power C
17
18
19
kW
SIGN = 1 means '-'
11
Power Factor A
20
21
LO/100
12
Power Factor B
22
23
SIGN = 0 means '+'
±
0 - 1.00
13
Power Factor C
24
25
SIGN = 1 means '-'
14
Total Active Power
26
27
kW
HI*10000+LO
0 - 5,184,000
15
System Power Factor
28
29
LO/100
SIGN = 0 means '+
SIGN = 1 means '-'
±
0 - 1.00
16
Active Energy
30
31
kWh
HI*10000+LO
0 - 99,999,000
17
Unbalanced Current
or Ground Leakage
32
A or
mA
LO
0 - 32767
18
Frequency
33
Hz
LO/10
45.0 - 65.0
19
Reactive Power A
34
35
36
kvar
HI*10000+LO
20
Reactive Power B
37
38
39
kvar
SIGN = 0 means '+'
±
0 - 5,184,000
21
Reactive Power C
40
41
42
kvar
SIGN = 1 means '-'
22
Apparent Power A
43
44
kVA
23
Apparent Power B
45
46
kVA
HI*10000+LO
0 - 5,184,000
24
Apparent Power C
47
48
kVA
25
Reactive Energy
49
50
51
kvarh
HI*10000+LO
SIGN = 0 means '+'
SIGN = 1 means '-'
-9,999,000 -
99,999,000
26
Total Reactive Power
52
53
54
kvar
HI*10000+LO
SIGN = 0 means '+'
SIGN = 1 means '-'
±
0 - 5,184,000
27
Total Apparent
Power
55
56
kVA
HI*10000+LO
0 - 5,184,000
28
Active Power
Maximum Demand
57
58
kW
HI*10000+LO
0 - 5,184,000
29
Accumulated Active
Power Demand
59
60
kW
HI*10000+LO
0 - 5,184,000
30
Error code
64
LO
see Table 4-1