PM175 Quick Start Guide
Setting the Communications
You communicate with the meter via a changeable COM1 communication port, or
through a second factory set serial RS-485/RS-422 COM2 port. Depending on
what was ordered, the COM1 port is equipped with an RS-232/RS-422/RS-485
serial interface, with a dial-up modem for communicating through public telephone
lines, or with an Ethernet module for communicating through the Internet.
To configure the PM175 communication via PAS:
1. Select Configuration from the Tools menu. Under the
Communication group of the Instrument Setup tab, select the
type of a connection for your device.
2. Enter the device communication address you assigned to the
PM175.
3. In the Sampling Rate box, select a rate at which PAS updates
data on your screen when you continuously poll the device in
the PAS Data Monitor.
The communication protocol and port settings in PAS must match the settings
made in your device.
COM1 Settings
Code
Parameter
Options
Description
Prot
Communications protocol
ASCII, rtu*, dnP3
ASCII, Modbus RTU or DNP3.0 protocol
rS
Port Interface, depends on
order
232 = RS-232
485 = RS-485
422 = RS-422
dial = Dial-up Modem
Eth.= Ethernet
For non-serial interfaces this is not changeable,
it is automatically detected by the meter
Addr
Device Address
Modbus: 1 (default) -247
DNP3.0: 0 (default) -255
bAud
Baud rate
300 - 115,200 bps (19,200 bps*)
dAtA
Data format
7E, 8E (7/8 bits, even parity), 8N* (8 bits, no parity)
7E data format should not be used with the Modbus RTU and DNP3
protocols
H.Sh
Handshaking (flow control)
nonE*=no flow control
SOFt=software (XON/XOFF)
HArd=hardware (CTS)
rtS
RTS mode
nonE* = not used
Forc = RTS is permanently asserted
CtrL = RTS is asserted during the transmission
COM2 Settings
Code
Parameter
Options
Description
Prot
Communications protocol
Rtu* = Modbus RTU
ASCII = Modbus ASCII
dnP3 = DNP3
The communications protocol supported by the
port
rS
Port Interface
485* = RS-485
422 = RS-422
Addr
Address
Modbus: 1*-247
DNP3: 0–65532
Device network address
bAud
Baud rate
300-115,200 bps
(19,200 bps*)
The port baud rate.
dAtA
Data format and parity
7E, 8N*, 8E
7E data format should not be used with the
Modbus RTU and DNP3 protocols