PM175 Quick Start Guide
Figure 9: PM175 Navigation buttons
Setup is performed directly from the display panel or via the communication ports
using PAS communication software.
In Data Display mode, the navigation buttons function as follows.
The MIN/MAX button switches to the Min/Max Maximum Demands display pages.
When briefly pressed again, it switches back to the common measurements
display.
The PQ/ESC button switches between different power quality/harmonic displays:
Total Harmonics, Individual Voltage and Current Harmonics, and Power Quality
parameters – short-term (Pst) and long-term (Plt) flicker, and voltage and current
negative sequence unbalance. When briefly pressed once again, it switches back
to the common measurements display.
The UP and DOWN arrow buttons, labeled by arrowheads, scroll forwards and
backwards through the display pages. Pressed briefly, they move one page
forward or backward. If you hold the button down, the display pages are scrolled
at rate of a twice per second.
Pressing both the UP and DOWN arrow buttons together returns to the first page
within the current display.
The SELECT button operates once it’s released. The button has two functions:
o
When pressed briefly, switches to programming mode.
o
When pressed together with the ENTER button for more than
5 seconds, it resets Min/Max records, maximum demands, or
energies depending on the currently displayed page. If the
meter is password protected, and a simple reset of data from
the display is not allowed, the action has no effect.
The ENERGY/ENTER button switches to the Energy display. If TOU registers are
configured in the meter, you can repeatedly press this button to scroll through all
available TOU registers. When briefly pressed once again, it switches back to the
common measurements display
Auto Return
If no buttons are pressed for 30 seconds while the display Auto Return option is
enabled, the display automatically returns to the main screen from any other
measurement display.
The Auto Return option is enabled through the Display Setup menu
Auto Scroll
If no buttons are pressed for 30 seconds while in the common measurements
display, and the Auto Scroll option is enabled in the meter, the display
automatically scrolls through all available pages. The scroll interval is adjustable in
the Display Setup menu.
To stop auto scrolling, briefly press the SCROLL button.
BG0456 REV.A2
8