RKI Instruments GD-K11D User Manual
Page 18

14 • Operation
Model GD-K11D Operator’s Manual
3. Adjust the INT switch to the “2” position.
The current alarm point appears on the display screen, and the SKIP light flashes.
4. Press the MODE button, and make sure 2 appears on the left side of the display
screen.
5. Use the
∆
and
∇
buttons to adjust the alarm point to the setting you want.
6. Press the SET button to confirm the new alarm point.
The SPAN light turns on indicating that the Model GD-K11D accepted the new
setting.
7. Return the INT switch to the “0” position to return to normal operation.
The SPAN and SKIP lights turns of.
8. Rotate the housing cover up to its original position, then secure the cover to the
housing with the thumbscrew.
Adjusting the Alarm Delay
The factory-set alarm delay is 3 seconds. The range of acceptable alarm delay settings is
0.5 to 60 seconds.
1. Loosen the thumbscrew at the top of the housing.
2. Rotate the housing cover toward the bottom of the housing to gain access to the
interior of the Model GD-K11D.
3. Adjust the INT switch to the “3” position.
The current alarm delay appears on the display screen, and the SKIP light flashes.
4. Press the MODE button, and make sure 3 appears on the left side of the display
screen.
5. Use the
∆
and
∇
buttons to adjust the alarm delay to the setting you want.
6. Press the SET button to confirm the new alarm delay.
The SPAN light turns on indicating that the Model GD-K11D accepted the new
setting.
7. Return the INT switch to the “0” position to return to normal operation.
The SPAN and SKIP lights turns of.
8. Rotate the housing cover up to its original position, then secure the cover to the
housing with the thumbscrew.