Installation, Mounting the model gd-k11d – RKI Instruments GD-K11D User Manual
Page 12

8 • Installation
Model GD-K11D Operator’s Manual
Installation
This section describes how to install the Model GD-K11D at the monitoring site. This
section includes procedures to mount the Model GD-K11D, connect sample lines to the
Model GD-K11D, and make power and other wiring connections to the Model GD-K11D.
Mounting the Model GD-K11D
CAUTION:
The Model GD-K11D is suitable for installation in indoor areas where general
purpose equipment is in use.
1. Select a mounting site that is representative of the monitoring environment. Consider
the following when you select the mounting site.
•
Select a site where the Model GD-K11D is not likely to be bumped or disturbed.
Make sure there is sufficient room to make wiring and sample line connections at
the bottom of the transmitter. Also make sure there is sufficient room to open the
housing cover and perform start-up, maintenance, and calibration procedures.
•
Select a site near the sampling area.
NOTE:
If your application does not require a specific mounting site, mount the
transmitter at approximately eye level.
Figure 2: Mounting the Model GD-K11D
GAS DETECTOR
MODEL
GD-K11D
Note 1: All measurements in inches.
7.3
8.2
7.3
8.4
9.1
9.8
1.2
.45
.48
Note 2: Model GD-K11D is 4.1 inches deep.
Note 3: Allow at least 2 feet in front of
Model GD-K11D to open housing door.
0.3 dia.
(4 times)