PAGE 54 — DCA-500SSK — PARTS AND OPERATION MANUAL (STD) — REV. #1 (04/14/01)

DCA-500SSK — GENERATOR SHUTDOWN PROCEDURE

Figure 52. Off/Manual Auto Switch (OFF)

Engine Shutdown
To shutdown the generator use the following procedure:

Figure 51. Engine Speed Switch

Figure 53. MPEC Engine Running

Status LED (OFF)

5. Verify that the "Engine Running" status LED (Figure

53) on the Microprocessor Engine Control Module
(MPEC) display is "OFF" (not lit).

NEVER stop the engine suddenly
except in an emergency. DO NOT use

the emergency stop switch as a method
of shutting down the engine. This switch

is ONLY to be used in the event of an

emergency.

To stop the engine in the event of an emergency, PUSH the
emergency stop button (Figure 54) inward. This button is
located on the generator's control panel, see page 34,
Figure 10.

Emergency Stop

CAUTION:

Figure 54. Emergency Stop Button

4. Place the Off/Manual/Auto Switch (Figure 52) in the "OFF/

RESET" position

2. Set the engine speed switch (Figure 51) to the idle (low)

position (If optional part installed).

6. Remove the load from the UVW terminal strip (Figure 32

page 49).

1. Place both the MAIN, GFCI and LOAD circuit breakers

to the "OFF position"

3. Let the engine cool by running it for 3-5 minutes with no

load applied.