Output terminal panel connections – Multiquip DCA400SSI User Manual
Page 29
DCA400SSI GENERATOR • OPERATION AND PARTS MANUAL — REV. #2 (11/03/08) — PAGE 29
OUTPUT TERMINAL PANEL CONNECTIONS
3Ø-480V UVWO Terminal Output Voltages
Jumper the voltage change-over board for 480V
1.
operation as shown in Figure 23. This confi guration
uses 6 jumper plates in 3 different positions. Remember
there are 2 jumper plates at every position. Every
jumper plate must be used.
Voltage Change-Over Board 480V
Figure 23.
Confi guration
Connect the load wires to the UVWO terminals as
2.
shown in Figure 24.
UVWO Terminal Lugs 3Ø-480V
Figure 24.
Connections
NOTICE
ALWAYS make sure that the connections to the UVWO
terminals are secure and tight. The possibility of arcing
exists, that could cause a fi re.
1Ø-480V UVWO Terminal Output Voltages
Make sure the voltage change-over board is jumpered
1.
for 480V operation as shown in Figure 23.
Connect the load wires to the UVWO terminals as
2.
shown in Figure 25.
UVWO Terminal Lugs 1Ø-480V
Figure 25.
Connections
1Ø-277V UVWO Terminal Output Voltages
Make sure the voltage change-over board is jumpered
1.
for 480V operation as shown in Figure 23.
Connect the load wires to the UVWO terminals as
2.
shown in Figure 26.
UVWO Terminal Lugs 1Ø-277V
Figure 26.
Connections