beautypg.com

General information – Multiquip DCA400SSI User Manual

Page 16

background image

PAGE 16 — DCA400SSI GENERATOR • OPERATION AND PARTS MANUAL — REV. #2 (11/03/08)

GENERATOR

The MQ Power Model DCA400SSI is a 320 kW generator
(Figure 3) that is designed as a high quality portable
(requires a trailer for transport) power source for telecom
sites, lighting facilities, power tools, submersible pumps
and other industrial and construction machinery.

ENGINE OPERATING PANEL

The “Engine Operating Panel” is provided with the following:

Tachometer

Emergency Stop Switch

Water Temperature Gauge

Oil Pressure Gauge

Charging Ammeter Gauge

Fuel Level Gauge

Pre-Heat Lamp

Engine Speed Switch

Battery Switch

Engine Alarm Lamps (5)

GENERATOR CONTROL PANEL

The “Generator Control Panel” is provided with the following:

Frequency Meter (Hz)

AC Ammeter (Amps)

AC Voltmeter (Volts)

Ammeter Change-Over Switch

Voltmeter Change-Over Switch

Voltage Regulator

Panel Light/Panel Light Switch

3-Pole, 1,000 amp Main Circuit Breaker

“Control Box” (located behind the Gen. Control Panel)

Automatic Voltage Regulator

Current Transformer

Over-Current Relay

Voltage Rectifi er

Starter Relay

Engine Controller (Computer Controlled)

Voltage Change-Over Board

OUTPUT TERMINAL PANEL

The “Output Terminal Panel” is provided with the following:

Three 120/240V output receptacles (CS-6369), 50A

Three auxiliary circuit breakers, 50A

Two 120V output receptacles (GFCI), 20A

Two GFCI circuit breakers, 20A

Eight output terminal lugs (3Ø power)

Battery Charger (Optional)

Water Heater (Optional)

OPEN DELTA EXCITATION SYSTEM

The DCA400SSI generator is equipped with the state of the
art “Open-Delta” excitation system. The open delta system
consist of an electrically independent winding wound
among stationary windings of the AC output section.
There are four connections of the open delta A, B, C and
D. During steady state loads, the power from the voltage
regulator is supplied from the parallel connections of A to
B, A to D, and C to D. These three phases of the voltage
input to the voltage regulator are then rectifi ed and are the
excitation current for the exciter section.
When a heavy load, such as a motor starting or a short
circuit occurs, the automatic voltage regulator (AVR)
switches the confi guration of the open delta to the series
connection of B to C. This has the effect of adding the
voltages of each phase to provide higher excitation to the
exciter section and thus better voltage response during the
application of heavy loads.
The connections of the AVR to the AC output windings are
for sensing only. No power is required from these windings.
The open-delta design provides virtually unlimited excitation
current, offering maximum motor starting capabilities. The
excitation does not have a “fi xed ceiling” and responds
according the demands of the required load.

ENGINE

The DCA400SSI is powered by a 6 cylinder, water cooled,
direct injection, turbocharged air-to-air ISUZU 6WG1X
Diesel Engine. This engine is designed to meet every
performance requirement for the generator. Reference
Table 2 for engine specifi cations.
In keeping with MQ Power’s policy of constantly improving
its products, the specifi cations quoted herein are subject
to change without prior notice.

ELECTRIC GOVERNOR SYSTEM

The electric governor system controls the RPMs of the engine.
When the engine demand increases or decreases, the
governor system regulates the frequency variation to ±.25%.

EXTENSION CABLES

When electric power is to be provided to various tools or
loads at some distance from the generator, extension cords
are normally used. Cables should be sized to allow for
distance in length and amperage so that the voltage drop
between the generator and point of use (load) is held to
a minimum. Use the cable selection chart (Table 6) as a
guide for selecting proper extension cable size.

GENERAL INFORMATION