GENERATOR OUTPUTS/GAUGE READING

Maximum Amps

Table 10 shows the maximum amps the generator can
provide. DO NOT exceed the maximum amps as listed.

HOW TO READ THE OUTPUT TERMINAL GAUGE

The AC ammeter and AC voltmeter change-over switches
on the control panel DO NOT effect the generator output.
They are provided to help observe how much power is being
supplied, produced at the UVWO terminals lugs.

When the voltage change-over board is jumpered for 3Ø,
240V operation (See Figures 14 and15), place the AC
Voltmeter Change-Over Switch
(See Figures 16 and 17)
to the W-U position and the AC Ammeter Change-Over
Switch
(Figure 16) to the U or W position to read the output
on the selected leg.

Voltage Change-Over Board 240V

Figure 13.

Confi guration

Generator Maximum Amps

Table 10.

Model

DCA400SSI

Rated Voltage

Maximum Amps

Single Phase 120 Volt

888.9 amps (4 wire)

Single Phase 240 Volt

444.4 amps (4 wire)

Three Phase 240 Volt

962.3 amps

Three Phase 480 Volt

481.1 amps

AC Voltmeter

Figure 14.

Change-Over Switch

AC Voltmeter

Figure 15.

Gauge (Volt reading on

W-U Lug)

AC Ammeter

Figure 16.

Change-Over Switch

AC Ammeter

Figure 17.

(Amp reading on U lug)

NOTICE

The ammeter gauge will only show a reading when
the Output Terminal Lugs are connected to a load
and in use.