GENERATOR OUTPUTS/GAUGE READING
Maximum Amps
Table 10 shows the maximum amps the generator can
provide. DO NOT exceed the maximum amps as listed.
HOW TO READ THE OUTPUT TERMINAL GAUGE
The AC ammeter and AC voltmeter change-over switches
on the control panel DO NOT effect the generator output.
They are provided to help observe how much power is being
supplied, produced at the UVWO terminals lugs.
When the voltage change-over board is jumpered for 3Ø,
240V operation (See Figures 14 and15), place the AC
Voltmeter Change-Over Switch (See Figures 16 and 17)
to the W-U position and the AC Ammeter Change-Over
Switch (Figure 16) to the U or W position to read the output
on the selected leg.
Voltage Change-Over Board 240V
Figure 13.
Confi guration
Generator Maximum Amps
Table 10.
Model
DCA400SSI
Rated Voltage
Maximum Amps
Single Phase 120 Volt
888.9 amps (4 wire)
Single Phase 240 Volt
444.4 amps (4 wire)
Three Phase 240 Volt
962.3 amps
Three Phase 480 Volt
481.1 amps
AC Voltmeter
Figure 14.
Change-Over Switch
AC Voltmeter
Figure 15.
Gauge (Volt reading on
W-U Lug)
AC Ammeter
Figure 16.
Change-Over Switch
AC Ammeter
Figure 17.
(Amp reading on U lug)
NOTICE
The ammeter gauge will only show a reading when
the Output Terminal Lugs are connected to a load
and in use.