Generator outputs, Generator output voltages, Voltage change-over board – Multiquip DCA250SSI_250SSIU User Manual
Page 26: Generator amperage maximum amps

PAGE 26 — DCA250SSI/DCA250SSIU GENERATOR • OPERATION AND PARTS MANUAL — REV. #0 (01/12/11)
GENERATOR OUTPUTS
GENERATOR OUTPUT VOLTAGES
A wide range of voltages are available to supply voltage
for many different applications. Voltages are selected by
applying jumpers (6) to the voltage change-over board
(Figure 12). To obtain some of the voltages as listed in
Table 7 (see below) will require a fi ne adjustment using
the voltage regulator (VR) control knob located on the
control panel.
Voltage Change-Over Board
The voltage change-over board (Figure 12) is located on
the control box, behind the generator control panel. This
board has been provided for ease of voltage selection.
Figure 12. Voltage Change-Over Board
CAUTION
NEVER attempt to place jumper plates on the voltage
change-over board while the generator is in operation.
There exist the possibility of electrocution, electrical
shock or burn, which can cause severe bodily harm
or even death!
Table 7. Voltages Available
UVWO Output
Terminal Lugs
Voltage Selector Switch
3-Phase 240/139V Position
Voltage Selector Switch
3-Phase 480/270V Position
3Ø
Line-Line
208V
220V
240V
416V
440V
480V
1Ø Line-Neutral
120V
127V
139V
240V
254V
277V
Voltage Selector Switch Single-Phase 240/120V Position
1Ø Line-Neutral/
Line-Line
120V
Line-Neutral
N/A
N/A
240V
Line-Line
N/A
N/A
Generator Amperage
Maximum Amps
Table 8 shows the maximum amps the generator can
provide. DO NOT exceed the maximum amps as listed.
Table 8. Generator Maximum Amps
Model
DCA250SSI/
DCA250SSIU
Rated Voltage
Maximum Amps
Single Phase 120 Volt
555.5 Amps (4 wire)
Single Phase 240 Volt
277.7 Amps (4 wire)
Three Phase 240 Volt
601 Amps
Three Phase 480 Volt
301 Amps