PAGE 26 — DCA-180SSK — PARTS AND OPERATION MANUAL — REV. #3 (06/11/09)

DCA-180SSK — GENERAL INFORMATION

DCA-180SSK FAMILIARIZATION

Generator

The MQ Power Model DCA-180SSK is a 144 kW

generator

that has been designed as a high quality portable (requires
a trailer for transport) power source for telecom sites, lighting
facilities, power tools, submersible pumps and other
industrial and construction machinery.

Engine Control Panel

The “Engine Control Panel” is provided with the following:
 Tachometer
 Water Temperature Gauge
 Oil Pressure Gauge
 Charging Ammeter Gauge
 Engine Speed Switch
 Pre-Heat Button
 Pre-Heat Lamp
 Emergency Stop Button
 Battery Switch
 Ignition Key Switch
 MPEC Module (on some models)

Generator Control Panel

The “Generator Control Panel” is provided with the following:
 Output Voltage Adjustment Knob
 Frequency Meter (Hz)
 AC Ammeter (Amps)
 AC Voltmeter (Volts)
 Ammeter Change-Over Switch
 Voltmeter Change-Over Switch
 Panel Light
 Panel Light Switch
 Pilot Lamp

Output Terminal Panel

The “Output Terminal Panel” is provided with the following:
 Two 120V GFCI receptacles, 20 amp
 Three 240/139V output receptacles, 50 amp
 Two 120V input receptacles, 20 amp
 3 Load Circuit Breakers 265V @65 amps
 2 Load GFCI Circuit Breakers 265V@ 20amps

Microprocessor Controlled Alarm System
The DCA-180SSK generator is equipped with various alarms
and LED status indicators. These alarms and status indicators
are provided to add safety to the generator when operating
under normal conditions. The DCA-180SSK generator is
designed to shutdown in the event of low oil, high coolant
temperature, low battery and other operation conditions that
may cause severe damage to the generator.

Open Delta Excitation System

The DCA-180SSK generator is equipped with the state of
the art "

Open-Delta" excitation system. The open delta

system consist of an electrically independent winding wound
among stationary windings of the AC output section.

There are four connections: A, B, C and D. During steady
loads, the power to the

Automatic Voltage Regulator (AVR)

is supplied from the parallel connections of A to B, A to D,
and C to D. These three phases are rectified and are used as
the current for the exciter section.

During a heavy load, such as motor starting, the AVR
switches the configuration of the Open-Delta to the series
connection B to C. This has the effect of adding the voltages
of each phase to provide better voltage response during heavy
loads.

The connections of the AVR to the AC output windings are
for the sole purpose of sensing. No power is required from
these windings.

The open-delta design provides virtually unlimited excitation
current due to its independent power supply offering maximum
motor starting capabilities. The excitation does not have a
"

fixed ceiling" and responds according the demands of the

required load.

Control Box

The “Control Box” is provided with the following:
 Main Circuit Breaker 500 amps
 Over-Current Relay
 High Idle Adjust Trimmer