Output terminal panel connections – Multiquip DCA150SSiU User Manual
Page 29
DCa150SSI/DCa150SSIu 60 hz gen. • operatIon anD partS manual — rev. #0 (11/23/09) — page 29
OUTPUT TErMINAL PANEL CONNECTIONS
3Ø-480/277V UVWO Terminal Output Voltages
Place the voltage selector switch in the 3Ø 480/277
1.
position as shown in Figure 24.
Voltage Selector Switch
figure 24.
3Ø-480/277V Position
connect the load wires to the UVWO terminals as
2.
shown in Figure 25.
UVWO Terminal Lugs
figure 25.
3Ø-440/254V Connections
Turn the voltage regulator knob (Figure 20) clockwise
3.
to increase voltage output, turn counterclockwise
to decrease voltage output. Use voltage regulator
adjustment knob whenever fine tuning of the output
voltage is required.
1Ø-240/120V UVWO Terminal Output Voltages
Place the voltage selector switch in the 1Ø 240/120
1.
position as shown in Figure 26.
Voltage Selector Switch
figure 26.
1Ø-240/120V Position
connect the load wires to the UVWO terminals as
2.
shown in Figure 27.
UVWO Terminal Lugs
figure 27.
1Ø-200/100V Connections
Turn the voltage regulator knob (Figure 21) clockwise
3.
to increase voltage output, turn counterclockwise to
decrease voltage output. Use voltage regulator
adjustment knob whenever fine tuning of the output
voltage is required.
NOTICE
alWaYS make sure that the connections to the UVWO
terminals are
secure and tight. The possibility of arcing
exists, that could cause a fire.