beautypg.com

Generator outputs, Generator output voltages, Voltage selector switch – Multiquip DCA150SSiU User Manual

Page 26: Voltage selector switch locking button, Generator amperage, Gfci receptacle load capability

background image

page 26 — DCa150SSI/DCa150SSIu 60 hz gen. • operatIon anD partS manual — rev. #0 (11/23/09)

gENErATOr OUTPUTS

generator output voltageS

A wide range of voltages are available to supply voltage for

many different applications. Voltages are selected by using

the

voltage selector switch (Figure 13). To obtain some of

the voltages as listed in Table 7 (see below) will require a

fine adjustment using the

voltage regulator (VR) control

knob located on the control panel.

Voltage Selector Switch

The voltage selector switch (Figure 13) is located above

the output terminal panel’s Hard Wire Hook-up Panel. It

has been provided for ease of voltage selection.

Voltage Change-Over board

figure 13.

Voltage Selector Switch Locking Button

The voltage selector switch has a locking button to protect

the generator and load from being switched while the

engine is running. To lock the voltage selector switch, press

and hold the red button located at the bottom of the switch.

cAUTION

never change the position of the voltage selector

switch while the engine is running. alWaYS place

circuit breaker in the

oFF position before selecting

voltage

.

voltages available

table 7.

Three Phase

(Switchable)

208V

220V

240V

416V

440V

480V

Single Phase

(Switchable)

120V

1127V

139V

240V

254V

277V

Generator Amperage

Table 8 shows the

maximum amps the generator can

provide.

Do not exceed the maximum amps as listed..

GFcI Receptacle Load capability

The load capability of the GFcI receptacles is directly

related to the voltage being supplied at either the output

terminals or the 2 twist lock auxiliary receptacles.
Tables 9 and 10 show what amount of current is available

at the GFcI receptacles when the output terminals and

twist lock receptacles are in use. Be careful that your load

does not to exceed the available current capability at the

receptacles.

generator maximum amps

Table 8.

rated voltage

maximum amps

1Ø 120 Volt

333.3 amps (4 wire)

1Ø 240 Volt

166.7 amps (4 wire)

3Ø 240 Volt

361 amps

3Ø 480 Volt

180 amps

1Ø gFCI receptacle load Capacity

table 9.

KW in Use

twist lock (C6369)

available load

Current (amps)

1Ø 240/120V

GFcI Duplex

5-20R 120V

87.0

0

85.8

5 amps/receptacle

84.6

10 amps/receptacle

83.4

15 amps/receptacle

82.2

20 amps/receptacle

Table 10.

gFCI receptacle load Capacity

Kva in use

(uvWo terminals)

available load

Current (amps)

3Ø 240/480V

GFcI Duplex

5-20R 120V

150

0 amps/receptacle

146

5 amps/receptacle

142

10 amps/receptacle

138

15 amps/receptacle

133

20 amps/receptacle

This manual is related to the following products: