3.2.2 Fusibles/section des câbles
Type
Installation selon EN 60204-1
Installation selon UL
DD
(2)
Fusible Disjoncteur
L1, L2, L3, PE
[mm²]
Fusible
(3)
L1, L2, L3, PE
[AWG]
1/N/PE
ETMD371L2YXA, ETMD551L2YXA
M10 A
C10 A
1,5
10 A
14
> 30 mA
ETMD751L2YXA
M16 A
C16 A
2,5
15 A
14
ETMD112L2YXA
M20 A
C20 A
2,5
15 A
12
ETMD152L2YXA
M25 A
C25 A
2,5
20 A
12
ETMD222L2YXA
M30 A
C30 A
4,0
30 A
10
3/PE
ETMD371L2YXA...ETMD112L2_XA
(4)
M10 A
C10 A
1,5
10 A
14
ETMD152L2_XA
(4)
M16 A
C16 A
1,5
12 A
14
ETMD222L2_XA
(4)
M16 A
C16 A
2,5
15 A
12
ETMD402L2TXA
M25 A
C25 A
4,0
25 A
10
ETMD552L2TXA
M40 A
C40 A
6,0
35 A
8
ETMD752L2TXA
M50 A
C50 A
10
45 A
8
ETMD371L4TXA...ETMD222L4TXA
M10 A
C10 A
1,5
10 A
14
ETMD302L4TXA
M16 A
C16 A
1,5
12 A
14
ETMD402L4TXA
M16 A
C16 A
2,5
15 A
14
ETMD552L4TXA
M20 A
C20 A
2,5
20 A
12
ETMD752L4TXA
M25 A
C25 A
4,0
25 A
10
(1) Respectez la réglementation locale en vigueur.
(2) Disjoncteur différentiel courant impulsionnel ou disjoncteur différentiel sensitif tout courant.
(3) Fusibles rapides de type UL Classe CC ou T limiteur de courant, 200 000 AIC, requis. Bussman KTK-R, JJN, JJS, ou équivalent.
(4) « _ » = Y ou T ; les caractéristiques sont identiques pour les deux modèles avec une entrée 3/PE.
CEM
Conforme à la norme EN 61800-3/A11
Perturbations radio-électriques : émission
Conforme à la valeur limite de la Classe A de la norme EN 55011 avec installation
dans un coffret électrique avec filtre “montage arrière” approprié et avec câble moteur
de 10m maxi.
A Colliers de blindage
B Câble de commande
C Câble moteur de faible capacité
(brin/brin < 75 pF/m, brin/blindage < 150 pF/m)
D Plaque de montage conductrice
E Filtre
Tmd005
B
E
C
D
A
3.2
Installation électrique
3.2.1 Installation conforme aux directives CEM