Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Lenze Selection
Configuration -
Digital input E1
1
1
Activate fixed setpoint 1 (JOG1)
Activate JOG3: Both terminals = HIGH
2
Activate fixed setpoint 2 (JOG2)
3
DC braking (DCB)
see also C36
4
Direction of rotation
LOW = CW rotation
HIGH = CCW rotation
Configuration -
Digital input E2
2
5
Quick stop
Controlled deceleration to standstill, active
LOW; Set decel rate in C13 or c03
6
CW rotation
7
CCW rotation
CW rotation = LOW and CCW rotation =
LOW: Quick stop; Open-circuit protected
Configuration -
Digital input E3
3
8
UP (setpoint ramp-up)
9
DOWN (setpoint ramp-down)
UP = LOW and DOWN = LOW: Quick stop;
Use momentary NC contacts
10 TRIP set
Active LOW, triggers
(motor coasts to
standstill)
NOTE:
NC thermal contact from the motor
can be used to trigger this input
Configuration -
Digital input E4
4
11 TRIP reset
see also c70
12 Accel/decel 2
see c01 and c03
Note
A
fault will occur under the following conditions:
• E1...E4 settings are duplicated (each setting can only be used once)
• One input is set to UP and another is not set to DOWN, or vice-versa
Network address
1
1
247 Each controller on network must have
unique address
C1
Minimum output
frequency
0.0
0.0
{Hz}
240 • Output frequency at 0% analog setpoint
• C10 not active for fixed setpoints or
setpoint selection via c40
Maximum output
frequency
50.0
7.5
{Hz}
240 • Output frequency at 100% analog setpoint
• C11 is never exceeded
WARNING!
Consult motor/machine manufacturer before operating above rated frequency.
Overspeeding the motor/machine may cause damage to equipment and injury to
personnel!
Acceleration time 1
5.0
0.0
{s}
999 • C12 = frequency change 0 Hz...C11
• C13 = frequency change C11...0 Hz
• For S-ramp accel/decel, adjust c82
Deceleration time 1
5.0
0.0
{s}
999