(1) The drive can only be restarted if the error message has been reset; see c70
Error
Cause
Remedy
(1)
External error
Digital input “TRIP set” is active
Remove external error
0
Internal fault
Please contact Lenze
Communication error
Serial timer has timed out
Check serial link connections
Communication error
Serial communication failure
Please contact Lenze
Remote keypad fault
Remote keypad disconnected
Check remote keypad connections
1
Drive identification fault
Attempt was made to perform motor
calibration before setting C86...C91
Must set C86...C91 before performing
motor calibration (see c48)
1
Short-circuit or overload
Short-circuit
Find reason for short-circuit; check
motor cable
Excessive capacitive charging
current of the motor cable
Use shorter motor cables with lower
charging current
Acceleration time (C12, c01) too short
• Increase acceleration time
• Check controller selection
Defective motor cable
Check wiring
Internal fault in motor
Check motor
Frequent and long overload
Check controller selection
Earth fault
Grounded motor phase
Check motor/motor cable
Excessive capacitive charging
current of the motor cable
Use shorter motor cables with lower
charging current
C
Motor overload (I
2
t
overload)
Motor is thermally overloaded, due to:
• impermissable continuous current
• frequent or too long acceleration
processes
• Check controller selection
• Check setting of c20
LP1
Loss of motor phase
Open-circuit on controller output when in
vector mode (C14 = 4, 5)
• Motor must be connected in vector
mode
• Check motor/motor cable
H
Controller
overtemperature
Controller too hot inside
• Reduce controller load
• Improve cooling
U
Overvoltage on DC bus
Mains voltage too high
Check mains voltage
Excessively short deceleration time or
motor in generator mode
Increase deceleration time or use
dynamic braking option
Earth leakage on the motor side
Check motor/motor cable
(separate motor from controller)
Flying restart fault
Controller was unable to synchronize with
motor during restart attempt
Check motor/load
Faulty auto-TRIP reset
More than 8 errors in 10 minutes
Depends on the error
Loss of 4-20 mA
reference
4-20 mA signal (terminal 8I) is below 2
mA (C34 = 5)
Check signal/signal wire
Single phase fault
A mains phase has been lost
Check mains voltage