Troubleshooting and fault elimination, System error messages general error messages – Lenze EVF9333−xV User Manual
Page 43
Troubleshooting and fault elimination
System error messages
General error messages
l
43
EDKVF93−03 EN 3.0
Remedy
Cause
Description
Fault message
Remedy
Cause
Description
Display
No.
x062
CE1
Communication error on the
process data input object
CAN1_IN
CAN1_IN object receives faulty
data or communication is
interrupted.
l
Check wiring at X4.
l
Check sender.
l
Increase monitoring time
under C0357/1, if necessary.
l
Switch off monitoring
(C0591 = 3).
x063
CE2
Communication error on the
process data input object
CAN2_IN
CAN2_IN object receives faulty
data or communication is
interrupted.
l
Check wiring at X4.
l
Check sender.
l
Increase monitoring time
under C0357/2, if necessary.
l
Switch off monitoring
(C0592 = 3).
x064
CE3
Communication error on the
process data input object
CAN3_IN
CAN3_IN object receives faulty
data or communication is
interrupted.
l
Check wiring at X4.
l
Check sender.
l
Increase monitoring time
under C0357/3, if necessary.
l
Switch off monitoring
(C0593 = 3).
x065
CE4
BUS−OFF state of system bus
(CAN)
The controller has received too
many faulty telegrams via the
system bus (CAN) and has
disconnected from the bus.
l
Check wiring at X4: Is the bus
correctly terminated?
l
Check shield connection of the
cables.
l
Check PE connection.
l
Check bus load, reduce the
baud rate if necessary.
(Observe the cable length!)
l
Switch off the monitoring
(C0595 = 3).
0071
CCr
System failure
Strong interference injection on
the control cables
Screen control cables
Ground or earth loops in the
wiring
l
Check wiring
l
Check PE connection
After troubleshooting: Deenergise
the device completely (disconnect
24 V supply, discharge DC bus)!
0072
PR1
Checksum error in parameter
set 1
CAUTION: The Lenze setting is
loaded automatically!
l
Fault when loading a
parameter set.
l
Interruption while
transmitting the parameter set
via keypad.
l
Set the required parameters
and store them under C0003 =
1.
l
As to PLC devices, check the
use of pointers.
The stored parameters are
incompatible with the loaded
software version.
Store the parameter set under
C0003 = 1 first to allow for a
faults reset.
0073
PR2
Checksum error in parameter
set 2
PLEASE NOTE: The Lenze setting is
loaded automatically!
l
Fault while loading a
parameter set.
l
Interruption during the
transfer of the parameter set
via keypad.
l
Set the required parameters
and save them with C0003 = 2.
The parameters saved do not
comply with the software version
loaded.
In order to be able to
acknowledge the error, first save
the parameter set with C0003 = 2.