Safety instructions
Safety instructions for the installation according to UL
l
19
EDKVF93−03 EN 3.0
Original − French
J
Warnings!
ƒ
Motor Overload Protection
– For information on the protection level of the internal overload protection
for a motor load, see the corresponding manuals or software helps.
– If the integral solid state motor overload protection is not used, external or
remote overload protection must be provided.
ƒ
Branch Circuit Protection
– The integral solid state protection does not provide branch circuit
protection.
– Branch circuit protection has to be provided externally in accordance with
corresponding instructions, the National Electrical Code and any
additional codes.
ƒ
Please observe the specifications for fuses and screw−tightening torques in
these instructions.
ƒ
EVF9330
EVF9333 :
– Convient aux circuits non susceptibles de délivrer plus de 10000 ampères
symétriques eff., maximum 480 V, avec protection par fusibles.
– Convient aux circuits non susceptibles de délivrer plus de 50000 ampères
symétriques eff., maximum 480 V, avec protection par des fusibles de
calibre J, T ou R.
– Température ambiante maximale : 0 ... +50 °C
– > +40 °C: ramener le courant assigné de sortie à 2,5 %/°C
– Utiliser exclusivement des conducteurs en cuivre 60/75 °C ou 75 °C.
ƒ
EVF9330
EVF9333 :
– Convient aux circuits non susceptibles de délivrer plus de 10000 ampères
symétriques eff., maximum 480 V, avec protection par fusibles.
– Convient aux circuits non susceptibles de délivrer plus de 50000 ampères
symétriques eff., maximum 480 V, avec protection par des fusibles de
calibre J, T ou R.
– Température ambiante maximale : 0 ... +50 °C
– > +40 °C: ramener le courant assigné de sortie à 2,5 %/°C
– Utiliser exclusivement des conducteurs en cuivre 60/75 °C ou 75 °C.