Installation – Lenze 8200 series User Manual
Page 27

Installation
UOMu_^MVMO
4-11
Terminal Use
(Factory setting is printed in bold)
Level
Data
Analog
i
t
7
GND 1
inputs
8
Setpoint input,
reference:
Terminal 7
(0 to 10V)
S
Q
O
R
P
N
5 - 6
5 - 6
3 - 4
1 - 2
0 to 20 mA
4 to 20 mA
0 to 5 V
0 to 10 V
Resolution: 9 bit
Linearity fault:
±0.5 %
Temperature fault: 0.3 % (0...+40
°C)
Input resistance
Voltage signal: > 100 kΩ
Jumper
Voltage signal: > 100 kΩ
Current signal: 250 Ω
9
Supply for setpoint potentiometer
5.2V / 6mA
Analog
output
62
Analog output, reference: terminal 7
(Field frequency)
0... 6 V / 2
mA
Resolution: 8 bit
Digital
inputs
20
Voltage supply for digital inputs
12 V/20 mA
p
28
Controller enable
HIGH
HIGH: 12 V ... 30 V
E4
CW rotation/
CCW rotation (CW/CCW)
CW: LOW
CCW: HIGH
HIGH: 12 V ... 30 V
LOW: 0 V ... 3 V
E3
DC-injection brake
HIGH
E2
JOG frequencies
Binary code
E1
JOG eque c es
20Hz, 30Hz, 40Hz
a y code
39
GND 2 (reference for external voltages)
Terminal Use
(Factory setting is printed in bold)
Relay position
(switched)
Data
Relay
output
K1
K 11
Relay output normally-closed contact
(TRIP)
opened
24 V AC / 3,0 A or
60 V DC / 0.5 A
p
K1
K 12
Relay mid-position contact
60 V DC / 0.5 A
K 14
Relay output normally-open contact
(TRIP)
closed