3 technical data, 1 general data/ application conditions, 1 general data/application conditions – Lenze 8200 series User Manual
Page 13: Technical data

Technical Data
UOMu_^MVMO
3-1
3 Technical data
3.1 General data/application conditions
Field
Values
Vibration resistance Germanischer Lloyd, general conditions
Humidity class
Humidity class F without condensation (average relative humidity 85 %)
Permissible
t
t
during transport of the controller: -25
°C ¼ +70 °C
Permissible
temperature ranges during storage of the controller: -25 °C ¼ +55 °C
during operation of the controller:
0
°C ¼+40 °C
+40
°C ¼ +50 °C
without power derating
with power derating
Permissible
installation height h
h ≤ 1000 m.a.m.s.l
1000 m a.m.s.l < h ≤ 4000 m a.m.s.l
without power derating
with power derating
Degree of pollution
VDE 0110 part 2 pollution degree 2
Noise emission
Requirements acc. to EN 50081-2, EN 50082-1, IEC 22G-WG4 (Cv) 21
Limit value class A to EN 55011 (industrial area) with mains filter
Limit value class B to EN 55022 (residential area) with mains filter and installation into
control cabinet
Noise immunity
Limit values maintained usig mains filter
Requirements according to EN 50082-2, IEC 22G-WG4 (Cv) 21
Requirements
Standard
Severities
ESD
EN61000-4-2
3, i.e. 8 kV with air discharge
6 kV with contact discharge
RF interference(enclosure)
EN61000-4-3
3, i.e. 10 V/m; 27
¼1000 MHz
Burst
EN61000-4-4
3/4, i.e. 2 kV/5 kHz
Surge
(Surge on mains cable)
EN 61000-4-5
3, i.e. 1.2/50 μs,
1 kV phase-phase,
2 kV phase-PE
Insulation strength
Overvoltage category III according to VDE 0110
Packaging
(DIN 4180)
Dust packaging
Type of protection
IP20
NEMA 1: Protection against contact
Approvals
CE:
Low Voltage Directive
Electromagnetic compatibility
Show/Hide Bookmarks