2 rated data (operation with 150 % overload), 1 types 8201 to 8204, Technical data – Lenze 8200 series User Manual
Page 14: 2 rated data

Technical Data
3-2
UOMu_^MVMO
3.2 Rated data
(Operation with 150 % overload)
3.2.1
Types 8201 to 8204
150 % overload
Type
8201
8202
8203
8204
Order no.
EVF8201-E
EVF8202-E
EVF8203-E
EVF8204-E
Variant ”reduced assembly
d th”
Type
8202-V002
Variant reduced assembly
depth”
Order no.
EVF8202-E- V002
Mains voltage
V
rated
[V]
190V 0% ≤ V
rated
≤ 260V 0% ; 45Hz¼65Hz 0%
Alternative DC supply
V
DC
[V]
270V 0% ≤ V
DC
≤ 360V 0%
Mains current
4)
with mains filter/mains choke
without mains filter/mains choke
I
mains
[A]
4.2
5.0
7.5
9.0
12.5
15.0
17.0
-
Data for mains operation with 1 AC / 230 V / 50 Hz/60 Hz; 270 ≤ V
DC
≤ 275V
Motor power (4 pole ASM)
t 9 2 kH *
P
rated
[kW]
0.37
0.75
1.5
2.2
oto po e ( po e S )
at 9.2 kHz*
P
rated
[hp]
0.5
1.0
2.0
2.9
Output power U, V, W
at 9.2 kHz*
S
N9.2
[kVA]
1.0
1.5
2.7
3.6
Output power +U
G
, -U
G
1)
P
DC
[kW]
0.0
0.0
0.0
0.0
Output current
I
rated
[A]
2.6
4.0
7.0
9.5
Max. output current for 60s
2)
I
Nmax
[A]
3.9
6.0
10.5
14.2
Motor voltage
3)
V
M
[V]
0 - 3 × V
mains
/ 0Hz
¼ 50Hz, if required up to 240Hz
Power loss (Operation with I
N
)
P
v
[W]
30
50
70
100
Show/Hide Bookmarks