N2 points – Lenze MCH Series Drives Metasys N2 User Manual
Page 14

11
RG-MHMET
N2 Points
Point
Description
3-05:
Keypad Setpoint Command
This point monitors and controls the Keypad Setpoint Command. The units for this point
are defined by Drive Parameter #31 (Units). The minimum and maximum values for this
point are defined by Drive Parameter #75 (Feedback @ Min) and #76 (Feedback @ Max),
respectively. The range of adjustment for Drive Parameters #75 and 76 is –32768 to
32767.
The ability to command this point through the N2 network is dictated by Drive Parameter
#30 (Control) and the drive HOA (Refer to Point 3-03). If this point is not being overridden,
this value can also be set using the drive’s MOP function or the UP and DOWN arrow keys
on the drive keypad.
NOTE: If the MOP function or the drive keypad is currently changing the keypad setpoint
command, serial override commands of this point will not be accepted.
4.5 Binary Output (BO) Point Descriptions
Point
Description
4-01:
Start/Stop Drive
This point reflects the last serial START/STOP command that was issued to the drive.
4-02:
Disable Serial Watchdog
This point is used to disable the drive's serial watchdog function. If this point is set to
NORMAL, then the serial watchdog will be enabled or disabled depending upon the setting
of Drive Parameter #57 (Serial). If this point is set to DISABLE then the serial watchdog is
DISABLED.
4-03:
Clear Present Fault
This point is used to clear the current fault via the serial link. Set this point to RESET (1)
to clear the present fault. Once the fault has been cleared, the value of this point will
automatically return to NORMAL (0).
4.6 Reference and Links
MCH Series Variable Frequency Drives visit:
http://www.lenze-actech.com
Metasys N2 and Johnson Controls, Inc. visit:
http://www.johnsoncontrols.com/publish/us/en/products/building_efficiency/building_
management/metasys.html